HIDRIA 0310-4-0139 Manual do utilizador - Página 3
Procurar online ou descarregar pdf Manual do utilizador para Ventilador HIDRIA 0310-4-0139. HIDRIA 0310-4-0139 8 páginas. Fan with electronically commutated external-rotor motor
02
PROPER USE AND TYPICAL & SPECIAL FEATURES
The fans are only intended for the transfer of air or air-like mixtures. They cannot be used in hazardous areas for the transfer of gas, mix vapours
or mixtures. Also cannot be used for transfer of solid components in transfer medium.
R10 axial fans with integrated external rotor ELECTRONICALLY COMMUTATED motor are not ready-to-use products, but designed as
components for air-conditioning, air supply and air extraction. The fans may only be operated when they are installed as intended & instructed,
and when safety is ensured by safety equipment according to EN 13857 or by other protection measures.
Axial fan is intended to be mounted on an air-conditioning, heat pump or evaporator heat exchanger housing with four screws so that the housing of application
prevents access to rotating parts from the rotor side and the protection grill prevents access to rotating parts from the front side. The heat exchanger's housing
prevents also access of water to axial fan from the rotor side.
This appliance is not intended to be built as a partition fan (mounting in outside windows or walls) unless it is built into an end-application which is
designed for that purpose.
The fan is intended to be permanently connected to fixed wiring.
The fans are only to be operated within the ranges specified on the motor name-plate.
Cycling operating mode: only with cycling via control signal (OFF=0V / ON=10V).
The manufacturer of the end application is responsible for keeping to the Electromagnetic compatibility (EMC) guideline 2014/30/CE.
Typical features
Variable Speed - setting via linear voltage input (0-10V) or PWM signal or other common way.
High efficiency throughout the entire speed range.
Low-noise operation across the entire speed range.
Integrated EMC filter.
External sensor power supply 10VDC (max 30mA).
Maintenance free ball-bearings and other components through the expected life-time.
The device is compatible with Modbus protocol RTU. Please read additional instructions about Hidria EC Modbus parameters and additional information for general
purpose using MODBUS (www.modbus.org) .
© Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
USER'S GUIDE R10 AXIAL FAN , Code: 0000, Iss: 3.02.2020
0