Automationdirect.com AcuAmp 3ACT Series Instruções de instalação

Procurar online ou descarregar pdf Instruções de instalação para Transdutor Automationdirect.com AcuAmp 3ACT Series. Automationdirect.com AcuAmp 3ACT Series 2 páginas.

Specifications
24 VAC/DC ( +/- 10%), Intended for use with a Class
2 source with the secondary fused to limit power to a
maximum of 100 VA
Power Supply
Note: Power Supply and output signal ARE NOT
isolated. Do not connect the negative terminals
to a common point.
Power Consumption
< 6.0 VA
4-20mA
Output Signals
Four outputs, three proportional to the current in that
phase, one an average of all three.
Output Limit
20.8 mA
Output Impedance
500Ω maximum
Accuracy
1.0% FS
Response Time
220ms (90% step change)
3ACT: 50/60Hz, Average Responding
Frequency Range
3ACTR: 30-100Hz, True RMS
1.1x range continuous
Sensed Current Limit
3x range for 6 seconds
6x range for 1 second
Isolation Voltage
UL tested to 1240VAC
Sensing Apertures
0.74 in (18.8 mm) dia.
Case
UL 94V-0 Flammability rated thermoplastic
-Temp -4 to 122°F (-20 to 50°C)
-Humidity 0-95% RH, Non-condensing
Environmental
-Pollution degree 2
-Altitude 2000 meters
cULus listed E197592
Certifications
CE
For products intended for the EU market, the
following is applicable to the CE compliance of
the product:
The 3ACT/3ACTR Series may comply with EN 61010-1 CAT III
300V max line-to-neutral measurement category. If insulated
cable is used for the primary circuit, the voltage rating of the
measurement category can be improved according to the
characteristics given by the cable manufacturer.
Part Number Key
3ACT030 - 42 - 24 - F
HOUSING TYPE
F - Fixed Core
POWER SUPPLY
24 - 24 VAC/DC (non-isolated)
OUTPUT SIGNAL
42 - 4-20mA
CURRENT RANGES
030 - 0-10, 0-15 and 0-30A
100 - 0-30, 0-50, and 0-100A
200 - 0-100, 0-150 and 0-200A
3ACT: 3-phase AC current transducer, average responding
3ACTR: 3-phase AC current transducer, True RMS
Warning! Risk of hazardous voltage
When operating the transducer, certain parts
may carry hazardous live voltage (e.g., primary
conductor, secondary terminals). The transducer
should not be put into service if the installation is
not complete.
Warning! Risk of electric shock or
personal injury
Safe operation can only be guaranteed if
the
is used for the purpose for
transducer
which it was designed and within the limits
of the technical specifications. When this
symbol is used, it means you should consult
all documentation to understand the nature
of potential hazards and the action required
to avoid them.
AutomationDirect.com (ADC)
3505 Hutchinson Road, Cumming, GA 30040
Phone: (800) 633-0405 or (770) 889-2858
3ACT/3ACTR - Inst - Rev 1
0820
P-N 292000612
3ACT/3ACTR
SERIES
INSTALLATION
INSTRUCTIONS
Part No. 3ACT030-42-24-F
Quick Start Guide
1. Mount the 3ACT/3ACTR Current Transducer to a
DIN rail or panel in a suitable enclosure.
2. With monitored load off, install each phase
through the sensing windows. Designate one
phase as A, B, and C.
3. Select the current range using the slide
switch
.
4. Connect output terminals + and - using 22-14
AWG copper wires rated 75/90°C. Tighten to 5-7
inch-pounds torque.
5. Connect power supply voltage to terminals 9-10.
6. The output will be proportional to the current in
each phase, plus one which is the average of the
three.
7. Any of the four analog signals can be used
independently, or all four can be used at the same
time.
®