ActivePure Induct Guardian I Manual - Página 4

Procurar online ou descarregar pdf Manual para Filtro de ar ActivePure Induct Guardian I. ActivePure Induct Guardian I 16 páginas.

RECOMMENDED INSTALLATION TOOLS

When the unit is installed in a roof mounted HVAC system, the unit must be
protected from elements.
Caution
3 1/2" Hole Saw
(for wood or metal)
YOU MAY ALSO NEED:
Utility Knife

INSTALLATION REQUIREMENTS

This unit must be installed by a licensed HVAC contractor or electrician. Failure
to do so will void warranty of the product.
Power Connection Requirements: This device is designed to operate using
a 24 VAC, 40Va transformer. Transformers supplied with a straight cooling
or HVAC system may be used to power the device but must be verified it's
capable of handling the additional device load before installation. If the system
WARNING
transformer is not capable of handing the extra load, a separate 24 VAC, 40Va
transformer MUST be used. Do not connect the device to any power source
with a voltage less than 22 VAC and a maximum of 32 VAC. Doing so will cause
damage to the device.
1.
Unit should be installed after the air handler in the
HVAC system.
2.
The ductwork around the installation area should be
clean and dry to ensure proper adhesion of the gasket
materials and any tape used.
3.
When installing near a furnace or heating coils, run
the heating system through five (5) full heating cycles
to ensure the temperature of the ActivePure
Guardian I unit does not exceed 200˚F.
4.
An approximate 3.5" (8.89 cm) opening will need
to be cut into the existing ductwork to install the
unit properly.
NOTE: Unit requires continuous power. Do not install where power to the unit will be cycled on and off.
4
Drill/Power
Phillips
Driver
Screwdriver
Tin Snips
(for metal ductwork)
®
3/8" Drill Bit
(if installing into
fiberglass ducting with
toggle bolts)
Dust Mask
Min. 9" x
9" Metal
Ductwork
Min. 10" x 10"
Fiberglass
Ductwork
Induct
Air Handle
1/4
1/4" Nut
Driver Bit
Max.
15 ft.