Procurar online ou descarregar pdf Manual técnico para Acessórios para câmaras Dynamis lead-line. Dynamis lead-line 16 páginas. Sealed lead acid batteries
may be used to evaluate the battery's condition.
There are several internal resistance measurement methods, and their
obtained values are sometimes different each other.
Conductance, i.e., the reciprocal of internal resistance, which is expressed as
mho or Siemens, has some kind of positive proportionate relationship with
the battery capacity.
3.5 Battery Life
Standby use battery life: 3 ~ 5 years under 2.3Vpc and 25°C floating charge
condition.
Cycle use battery life: 200 cycles (100%DOD)
DYNAMIS Batterien GmbH
Tel. +49 7735 93669-0
225 cycles (80%DOD)
500 cycles (50%DOD)
Brühlstr. 15 D-78465 Dettingen / Konstanz
Fax +49 7735 93669-91
www.dynamis-batterien.de
04.12.2006