Autonics TCN4 24 Series Manual do produto - Página 3

Procurar online ou descarregar pdf Manual do produto para Controlador de temperatura Autonics TCN4 24 Series. Autonics TCN4 24 Series 6 páginas. Dual display pid temperature controller

Autonics TCN4 24 Series Manual do produto
Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Decimal
Input type
point
1
K (CA)
0.1
1
J (IC)
0.1
1
Thermo
L (IC)
-couple
0.1
1
T (CC)
0.1
R (PR)
1
S (PR)
1
1
Cu50 Ω
0.1
RTD
1
DPt100 Ω
0.1
■ Display accuracy
Using
Input type
temperature
At room
temperature
(23℃ ±5 ℃)
Thermocouple
RTD
Out of room
temperature
range
• For TCN4S-□-P, add ±1℃ by accuracy standard.
• If the input specification is set to 'decimal point 0.1' display, add ±1℃ by accuracy standard.

Unit Descriptions

1
3
3
2
4
3. Indicator
Display
Name
Description
Alarm
Turns ON when the alarm
AL1/2
output
output is ON.
control
Turns ON when
output is ON
Control
• CYCLE/PHASE control of
OUT
output
SSR drive output: Turns ON
when MV is over 3.0%
[AC power model]
Auto
Flashes during auto tuning
AT
tuning
every 1 sec
Displays selected unit
℃, %, ℉
Unit
(parameter).
Errors
Display Description
Flashes when input sensor is disconnected or
sensor is not connected.
OPEN
HHHH Flashes when PV is higher than input range.
LLLL Flashes when PV is lower than input range.
Display
Using range (℃)
Using range (℉)
-50 to 1,200
KCaH
-50.0 to 999.9
-58.0 to 999.9
KCaL
-30 to 800
JIcH
-30.0 to 800.0
-22.0 to 999.9
JIcL
-40 to 800
LIcH
-40.0 to 800.0
-40.0 to 999.9
LIcL
-50 to 400
TCcH
-50.0 to 400.0
-58.0 to 752.0
TCcL
0 to 1,700
RPR
0 to 1,700
SPR
-50 to 200
CUsH
-50.0 to 200.0
-58.0 to 392.0
CUsL
-100 to 400
-148 to 752
DPtH
-100.0 to 400.0
-148.0 to 752.0
DPtL
Display accuracy
(PV ±0.5% or ±1 ℃ higher one) ±1-digit
• Thermocouple R, S below 200 ℃:
(PV ±0.5% or ±3 ℃ higher one) ±1-digit
Over 200 ℃:
(PV ±0.5% or ±2 ℃ higher one) ±1digit
• Thermocouple L, RTD Cu50 Ω:
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
• Thermocouple R, S below 200 ℃:
(PV ±1.0% or ±6 ℃ higher one) ±1digit
Over 200 ℃:
(PV ±0.5% or ±5 ℃ higher one) ±1digit
• Thermocouple L, RTD Cu50 Ω:
(PV ±0.5% or ±3 ℃ higher one) ±1digit
1. PV Display part (red)
RUN mode: Displays PV (Present value)
Setting mode: Displays parameter name
2. SV Display part (green)
RUN mode: Displays SV (Setting value)
Setting mode: Displays parameter setting value
4. Input key
Display
Name
[MODE]
Mode key
Setting value
[◀], [▼], [▲]
control key
Troubleshooting
Check input sensor status.
When input is within the rated input
range, this display disappears.
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
• Below is based on TCN4S Series .
A
-58 to 2,192
-22 to 1,472
-40 to 1,472
-58 to 752
Body
A
32 to 3,092
TCN4S
48
32 to 3,092
-58 to 392
TCN4S-□-P 48
TCN4M
72
TCN4H
48
TCN4L
96
■ Bracket
TCN4S
□49.5
60.3

Installation Method

■ TCN4S
Flathead screwdriver
Insert the unit into a panel, fasten the bracket by pushing with a flathead screwdriver.
Crimp Terminal Specifications
• Unit: mm, Use the crimp terminal of follow shape.
a
b
Wire ferrule
Terminal
a
number
1 to 8
6
9 to 11
6 to 8 ≤ 2.1 ≤ 4.2
12 to 14
6 to 8 ≤ 1.5 ≤ 3.5
C
D
Panel cut-out
B
C
D
E
F
48
6
64.5
44.8
≥ 65
48
7.7
65.8
44.8
≥ 65
72
6
64.5
67.5
≥ 90
96
6
64.5
91.5
≥ 65
96
6
64.5
91.5
≥ 115
Other series
30.5
46
12
23.9
■ Other series
≥3.0
c
≤5.8
Fork crimp terminal
b
c
≤ 1.7 ≤ 3.7
■ Panel cut-out
F
H
G
H
I
≥ 65
45
45
+ 0.5
+ 0.5
0
0
≥ 65
45
45
+ 0.5
+ 0.5
0
0
≥ 90
68
68
+ 0.7
+ 0.7
0
0
≥ 115
45
92
+ 0.6
+ 0.8
0
0
≥ 115
92
92
+ 0.8
+ 0.8
0
0
Flathead screwdriver
≥3.0
≤5.8
Round crimp terminal