Temperature Range Setting
Connect a HART communicator and set temperature range as
below by a HART communicator.
① Press the
key for 3 sec.
Select the '4. PV LRV' by
Online (Generic)
1. Device Setup
2. PV
3. PV Ao
4. PV LRV
5. URV
SAVE
② Select '1. PV LRV'(Low temperature range) and
press the
key.
1. PV LRV
2. URV
HELP
HOME
③ Set Low temperature range and press the
PV LRV
0.000 deg C
0.000
HELP
DEL
ESC
④ Select '2. URV'(High temperature range) and
press the
key.
1. PV LRV
2. URV
HELP
HOME
⑤ Set High temperature range and press the
PV URV
100.000 deg C
100.000
HELP
DEL
ESC
⑥ When the set temperature range is correct,
press the
(F2) key.
1. PV LRV 0.000 deg C
2. URV 100.000 deg C
HELP
SEND
HOME
⑦ Press the
(F4) key.
- WARNING -
Pressing ' OK ' will
change device output
put 100P in manual
⑧ Press the
(F4) key.
- WARNING -
Return control 100P
To automatic control
O K
⑨ Check the set temperature range. Press the
key. HART communication is OFF.
1. PV LRV 0.000 deg C
2. URV 100.000 deg C
HELP
HOME
keys and press the
key.
,
(F4) key.
ENTER
(F4) key.
ENTER
(F3)
Temperature Transmitter
Error Display And Troubleshootings
Display
Error
Temperature sensor
ERR05
A, B or all sensors are
disconnected.
ERR06 Temperature sensor B
is disconnected.
When PV is lower than
ERR07
the low-limit value of set
temperature range.
When PV is higher than
ERR08
the high-limit value of
set temperature range.
Proper Usage
Cautions During Use
• For connecting the power, use a crimp terminal
(M3.5, max. 7.2mm).
• The connection of this unit should be separated from
the power line and high voltage line in order to prevent
inductive noise.
• Install a power switch or a circuit breaker to supply or cut
off the power.
• Switch or circuit breaker should be installed nearby
users for convenient control.
• Do not use this unit near the high frequency instruments
(high frequency welding machine & sewing machine,
large capacity SCR controller).
• Installation environment.
① Indoor / Outdoor
② Altitude max. 2,000m
③ Pollution degree 2
④ Installation category Ⅱ
• Use the verified explosion-proof electric connection
(cable gland or sealing fitting)
(explosion proof standard: over Ex d IIC T6,
IP rating: over IP67 protection structure).
• Use the dedicated external terminal for earth. For
connecting earth, use a spring washer and earth cable
2
which is over 4mm
.
• We are not responsible for any damages and claims
for careless. Must read the cautions for your safety
and using.
• This explosion-proof unit is certified and the same
specifications which is reported to Korea Gas Safety
Corporation.
• If there are any problems with the unit, contact the
head office.
• Failure to follow these instructions may result in
product damage.
A. Recorder
Troubleshooting
B. Indicator
Check the temperature
C. Converter
sensor.
D. Controller
Check low-limit value
of the set temperature
range.
E. Thyristor
unit
Check high-limit value
of the set temperature
F. Pressure
range.
transmitter
G. Temp.
transmitter
H. Accessories
KT-502H