Autonics MT4N-DV Series Manual do produto - Página 4

Procurar online ou descarregar pdf Manual do produto para Instrumentos de medição Autonics MT4N-DV Series. Autonics MT4N-DV Series 6 páginas. 4-digit multi panel meters

Autonics MT4N-DV Series Manual do produto
■ Parameter 2 group
Parameter
Mark
Defaults Setting range
OUT1
2-1
operation
OU!T
OFF
mode
OUT2
2-2
operation
OU@T
OFF
mode
OUT1
2-3
hysteresis
HYs1
0)01
OUT2
2-4
hysteresis
HYs2
0)01
Startup
2-5
compensation
STaT
0)0
time
Peak
2-6
monitoring
00 S 00 to 30 sec
PEkT
delay time
2-7
Display cycle
)2 S 0.1 to 5.0 sec
DIsT
Current value
2-8
display part
COLR
RED
color
Keys for zero
2-9
adjustment
ZERO
NO
External
2-10
input
EVLN
HOLD
terminal
5)00
High-limit
50)0
value of
2-11
transmission
FS-H
output
25)0
%000
0)00
Low-limit
00)0
value of
2-12
transmission
FS-L
output
)0
)000
Comm.
2-13
Address
ADRS
01
Comm.
2-14
speed
BPS
9600
2-15 Parity bit
PRTY
NONE
2-16 Stop bit
STP
Response
2-17
waiting time
RSwT
2-18 Lock
LOC
OFF
[OUT1 output model]
OFF, HI, LO, HL, HL-G
• Refer to Output Operation Mode
[OUT2 output model]
OFF, HI, LO, HL, HL-G
• Refer to Output Operation Mode
[Except indicator model]
Within 10 % of max. display range, digit
[Except indicator model]
Within 10 % of max. display range, digit
[Except indicator model]
0.0 to 99.9 sec
RED: red / red, GRN: green / green,
YEL: yellow / yellow, R-G: red / green,
G-R: green / red
• Display: normal / error occurs
NO, YES
• YES: Press the [◀] + [▲] keys for 3
sec to adjust zero.
[Except indicator model]
HOLD, ZERO
• If the external input terminal is
short-circuited for 50 ms or more, it
operates with the set function.
[DC voltage & Transmission (DC 4 - 20
mA) output model]
Max. value of display range
[DC current & Transmission (DC 4 - 20
mA) output model]
Max. value of display range
[AC voltage & Transmission (DC 4 - 20
mA) output model]
Max. value of display range
[AC current & Transmission (DC 4 - 20
mA) output model]
Max. value of display range
[DC voltage & Transmission (DC 4 - 20
mA) output model]
Min. value of display range
[DC current & Transmission (DC 4 - 20
mA) output model]
Min. value of display range
[AC voltage & Transmission (DC 4 - 20
mA) output model]
Min. value of display range
[AC current & Transmission (DC 4 - 20
mA) output model]
Min. value of display range
[RS485 communication output model]
01 to 99
[RS485 communication output model]
38.4k, 19.2k, 9600, 4800, 2400, 1200 bps
[RS485 communication output model]
NONE, EVEN, ODD
[RS485 communication output model]
2, 1 bit
2
[RS485 communication output model]
5 to 99 sec
5
OFF: unlock,
LOC1: lock parameter 1,
LOC2: lock parameter 1, 2,
LOC3: lock parameter 0, 1 and 2
■ Parameter 0 group
Display
Parameter
condition
-
OUT1 high-
0-1
limit output
setting value
-
2-1 OUT1
operation
mode:
OUT1 low-
except
0-2
limit output
setting value
OFF
2-2 OUT2
operation
mode:
OUT2 high-
except
0-3
limit output
OFF
setting value
-
OUT2 low-
0-4
limit output
setting value
-
Display max.
-
0-5
peak value
01)
-
Display min.
-
0-6
peak value
01)
01)  Reset: Press any one of [◀], [▼], [▲] keys.
-
Input Range and Display Range
When the max. input value is over the 100 %, it may result in input terminal damage.
■ DC voltage model
Display range
-
Input range
Diaplay method: STND (fixed) Diaplay method: SCAL
0 - 50 VDCᜡ
0.00 to 50.00
0 - 10 VDCᜡ
0.00 to 10.00
0 - 5 VDCᜡ
0.000 to 5.000
0 - 1 VDCᜡ
0.000 to 1.000
0 - 250 mVDCᜡ
0.0 to 250.0
0 - 50 mVDCᜡ
0.00 to 50.00
01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
■ DC current model
-
Display range
Input range
Diaplay method: STND (fixed) Diaplay method: SCAL
0 - 500 mA
0.0 to 500.0
0 - 200 mA
0.0 to 200.0
0 - 50 mA
0.00 to 50.00
4 - 20 mA
4.00 to 20.00
-
0 - 5 mA
0.000 to 5.000
0 - 2 mA
0.000 to 2.000
-
01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
-
■ AC voltage model
-
Display range
Input range
Diaplay method: STND (fixed) Diaplay method: SCAL
-
0 - 250 VACᜠ
0.0 to 250.0
0 - 125 VACᜠ
0.0 to 125.0
0 - 50 VACᜠ
0.00 to 50.00
-
0 - 25 VACᜠ
0.00 to 25.00
0 - 5 VACᜠ
0.000 to 5.000
0 - 2.5 VACᜠ
0.000 to 2.500
01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
■ AC current model
Display range
Input range
Diaplay method: STND (fixed) Diaplay method: SCAL
0 - 5 A
0.000 to 5.000
0 - 2.5 A
0.000 to 2.500
0 - 500 mA
0.0 to 500.0
0 - 250 mA
0.0 to 250.0
0 - 100 mA
0.0 to 100.0
0 - 50 mA
0.00 to 50.00
01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
Mark
Defaults Setting range
[DC voltage model], [DC current model]
-5 to 110 % of display range
5)00
[AC voltage model]
0 to 110 % of display range
OU!H
25)0
[AC current model]
0 to 110 % of display range
%000
[DC voltage model]
-5 to 110 % of display range
0)00
[DC current model]
-5 to 110 % of display range
[AC voltage model]
OU!L
00)0
0 to 110 % of display range
[AC current model]
0 to 110 % of display range
)000
5)00
• Same as setting range of OUT1 high-
limit output setting value
25)0
OU@H
%000
• Same as setting range of OUT1 low-
0)00
limit output setting value
OU@L
00)0
)000
[DC voltage model]
Max. peak value in run mode
)00
[DC current model], [AC voltage model]
Max. peak value in run mode
hPEK
)0
[AC current model]
Max. peak value in run mode
)000
[DC voltage model]
Min. peak value in run mode
)00
[DC current model], [AC voltage model]
Min. peak value in run mode
lPEK
)0
[AC current model]
Min. peak value in run mode
)000
Decimals
50
0 -1999 to 9999
10
)0 -199.9 to 999.9
5
)00 -19.99 to 99.99
1
)000 -1.999 to 9.999
250
50
Decimals
500
0 -1999 to 9999
200
)0 -199.9 to 999.9
50
)00 -19.99 to 99.99
4-20
)000 -1.999 to 9.999
5
2
Decimals
250
0 -1999 to 9999
125
)0 -199.9 to 999.9
50
)00 -19.99 to 99.99
25
)000 -1.999 to 9.999
5
@5
Decimals
5
0 -1999 to 9999
@5
)0 -199.9 to 999.9
500
)00 -19.99 to 99.99
250
)000 -1.999 to 9.999
100
50
Display
condition
2-1 OUT1
operation
mode:
except
OFF
2-2 OUT2
operation
mode:
except
OFF
2-1 OUT1
operation
mode:
except OFF
or
2-2 OUT2
operation
mode:
except OFF
&
2-6 Peak
monitoring
delay time:
except 00
Input
impedance
01)
433.48 kΩ
Display range
433.48 kΩ
43.48 kΩ
43.48 kΩ
2.28 kΩ
2.28 kΩ
Input
impedance
01)
0.22 Ω
Display range
0.22 Ω
2.22 Ω
2.22 Ω
22.22 Ω
22.22 Ω
Input
impedance
01)
1.086 MΩ
Display range
1.086 MΩ
199.12 kΩ
199.12 kΩ
19.12 kΩ
19.12 kΩ
Input
impedance
01)
0.01 Ω
Display range
0.01 Ω
0.19 Ω
0.19 Ω
1.01 Ω
1.01 Ω