Description of Function

■ Zero blanking (timer)
PV is displayed with zero blanking for the highest unit.
• E.g.) When time range is 99m59.99s and PV is 00m04.05s.
Display value: 0:04.05
■ Start Point (counter)
This function is that start at initial value set at Start Point value.
• When reset is applied, the present value is initialized to Start Point value.
• After Count Up at output operation mode: C, R, P, Q, present value starts at Start Point value.
• If you change the start point value and return to RUN mode, the present value is changed to
the start point value.
• If the Start Point value is changed in the function setting mode, the present value is reset.
• Start Point value setting range is linked to C1-8 Counting value / preset value decimal point
position.
■ Prescale (counter)
This function is to set and display calculated unit for actual length, liquid, position, etc. It is
called 'prescale value' for measured length, liquid, or position, etc per 1 pulse.
• When moving L, the desired length to be measured, and P, the number of pulses per 1
revolution of a rotary encoder, occurs, prescale value is L/P.
• Application
Diameter of pulley connected with encoder is 22 mm, the number of pulses by 1 rotation of
encoder is 1,000
Pulley
Cutter
Rotary encoder
Motor
Counter
Motor control system
• Select decimal point: -----.-, prescale decimal point: ---.--- and set prescale value: 0.069,
it is available to control conveyor position by 0.1 mm unit.

Counter Operation

■ Input operation mode
Rising:
/ Falling:
Mode
Counting chart
01)
H
INA
L
A
A
H
INB
L
UP
No counting
Counting
value
2
1
0
H
INA
L
A
H
INB
L
UP - 1
No counting
Counting
2
value
1
0
H
INA
L
A
H
INB
UP - 2
L
No counting
Counting
2
value
1
0
H
INA
L
H
INB
L
UP - 3
Counting
2
value
1
0
H
INA
L
A
A
H
INB
L
DN
n n-1
No counting
n-2
n-3
Counting
value
0
H
INA
L
A
H
INB
L
DN - 1
n
No counting
n-1
n-2
Counting
n-3
value
0
01)  A should be over min. signal width, B is over 1/2 of min. signal width. If the signal is smaller than these widths, it
may cause counting error (±1).
π × Diameter of pulley
Prescale value =
The number of pulses by 1
rotation of encoder
3.1416 × 22
=
1000
= 0.069 mm / pulse
Operation
description
No counting
• INA: Counting input
A
A
INB: No counting
6 7
5
• INB: Counting input
4
3
INA: No counting
When INA input signal
A
is rising, it counts.
5
• INA: Counting input
4
3
INB: No counting
When INA input signal
A
is falling, it counts.
4
• INA: Counting input
3
INB: No counting
When INA and INB
input signals are rising,
it counts.
6
5
• INA: Counting input
3
INB: Counting input
No counting
• INA: Counting input
A
A
INB: No counting
• INB: Counting input
n-4
INA: No counting
n-5
n-6
n-7
When INA input signal
A
is rising, it counts.
• INA: Counting input
INB: No counting
n-4
n-5
Mode
Counting chart
INA
INB
DN - 2
Counting
value
INA
INB
DN - 3
Counting
value
INA H
UD - A
INB
: command
input
Counting
value
INA
UD - B
INB
: individual
input
Counting
value
INA
UD - C
: phase
INB
different
Counting
input
value
01)  A should be over min. signal width, B is over 1/2 of min. signal width. If the signal is smaller than these widths, it
may cause counting error (±1).
• Min. signal width by counting speed
Counting speed
[cps
]
01)
1
30
300
1 k
5 k
input
20
01)  1 cps = 1 Hz
input
H
INA
ON
(INB)
L
T.on
input
input
input
input
input
01)
H
L
A
A
H
L
n
No counting
n-1
n-2
n-3
0
H
L
H
L
n
n-1
n-2
n-3
0
L
A
A
H
L
4
3
3
2
2
1
1
0
H
L
H
L
4
3
3
2
2
2
1
0
H
L
BBBB
H
L
3
2
2
1
1
0
Min. signal width [ms]
CX6□-□P□
CX6□-□P□F
500
16.7
1.67
-
0.5
0.1
-
25
• H,L of the counting chart
OFF
ON
OFF
Input logic
T.off
Character
T.on, T.off
H
: min. signalwidth
T
L
Operation
description
When INA input signal
is falling, it counts.
• INA: Counting input
INB: No counting
n-4
input
n-5
When INA and INB
input signals are rising,
it counts.
• INA: Counting input
n-5
INB: Counting input
n-6
INB: In case of L,
count up
INB: In case of H,
count down
4
3
• INA: Counting input
2
INB: Counting
command input
When INA and INB
input signals are rising
at the same time, it
maintains previous
counting value.
4
3
• INA: Up counting
input
INB: Down counting
input
When connecting
encoder output A, B
phase with counter
3
input INA and INB, set
2
input operation mode
as UD-C.
Voltage
No-voltage
input (PNP)
input (NPN)
5 - 30 VDCᜡ Short
0 - 2 VDCᜡ
Open