DynaQuip WaterCop Pro WPCH Manual de início rápido - Página 3
Procurar online ou descarregar pdf Manual de início rápido para Unidade de controlo DynaQuip WaterCop Pro WPCH. DynaQuip WaterCop Pro WPCH 4 páginas.
Wireless Sensors
1. Before installing the wireless sensors, keep them
all near the Water Control Panel. Ensure the
sensors have batteries installed or are plugged into
a standard outlet nearby for adding into the system.
Valve must be open for programming where the
display reads "WATERCOP NORMAL".
2. On the Water Control Panel, press the "MODE"
button twice waiting a few seconds between each
button press until the display reads "DEVICE ADD /
PRESS NEXT
".
3. Press "CLOSE", which is indicated by the "NEXT
to put the Water Control Panel into add mode. The
display should read, "DEVICE ADD / DEV#_ ID=".
4. Take one sensor and short the probe to add the
sensor into the system. For Dual Sensors, only one
probe needs to be shorted to add the sensor into
the system. For Temperature Sensors, short the
moisture probe rather than the temperature sensing
probe.
5. Once the sensor has been added into the system
(which is indicated by the Water Control Panel
beeping and reading "DEVICE STATUS / SEN#__
SHORT1") wait until the display reads "DEVICE
STATUS / SEN# __ OK!".
6. Press "MODE" once to go back to the "DEVICE
ADD" display. (*If time has passed and the display
reads "WATERCOP NORMAL"; go back to step 2.)
7. Repeat steps 3-6 for each sensor to add them all
into the system.
8. At the same time, be sure to number them
according to the order they are added into the
system. You'll need this to record them in the
Sensor Location Log (included) when you put
them in location.
9. When all of the sensors have been added into the
system, you are ready to test them.
10. Test the sensors by individually getting them wet
and waiting until the alarm goes off and closes
the valve.
KEEP FINGERS AND OTHER OBJECTS
AWAY FROM VALVE TO AVOID INJURY.
11. Silence the Water Control Panel by pressing any
button once AFTER the valve has fi nished closing.
12. Remove the source of wetness from the sensor
"
probe and dry it off completely.
13. Wait until the display reads "!ALARM! SEN#__ OK".
14. Press the "OPEN" button to open the valve and
continue.
15. Repeat steps 10-14 for each sensor probe.
16. Now you can install the wireless sensors following
the "Installing the Wireless Sensors" and "Placement
of Wireless Sensors" sections of the Instruction
Manual to properly install the sensors.
Optional Features
•
Dry Contact Trouble Relay (See wiring guide on page
3 for location.) Dry contact closure for any alerts.
•
Dry Contact Alarm Relay (See wiring guide on page 3
for location.) Dry contact closure for any alarm caused
by a sensor getting wet and closing the valve.
•
12VDC Signal to operate an external relay for water
pump, recirculating pump, second valve, etc.
(See on page 3 for location.)
•
RJ45 Port is for the optional wall switch (RS100) or
Wi-Fi Interface Module.
•
Safe Mode is an optional feature that is user enabled
allowing the valve to close each time power is
restored after any outage.