Autonics CN-610 Series Manual do produto - Página 3
Procurar online ou descarregar pdf Manual do produto para Conversor de multimédia Autonics CN-610 Series. Autonics CN-610 Series 6 páginas. Isolated converters
Specifications
Model
CN-610□-□
Universal
- Temperature sensor
Input type
01)
: RTD, thermocouple
- Analog: voltage, current
12-segment (selectable red, green, yellow) LCD (character size: 6.4 ×
11.0 mm),
Display method
Graphic bar and input type / unit display part (red) LCD (character size:
1.4 × 2.75 mm)
Display accuracy
Dependent on the ambient temperature
02)
25 ± 5°C
± 0.2 % F.S. ± 1 digit
-10 to 20°C, 30 to 50°C ± 0.3 % F.S. ± 1 digit
Display cycle
-
03)
Temperature sensor input: 250 ms
Sampling cycle
Analog input: 100 ms
Unit weight
≈ 160 g (≈ 301 g)
(packaged)
Approval
ᜢ ᜫ
01) For details, refer to the input type and range.
02) Thermocouple, below -100 ℃: ± 0.4 % F.S. ± 1 digit
Thermocouple T, U: min. ± 2.0 ℃
03) When pulse input cycle is over 10 sec, it is updated by every 10 sec.
Transmission
Output
(DC 0 - 20 mA)
≤ 600Ω
Load resistance
Accuracy
± 0.3 F.S.
Resolution
8,000
-
Contact capacity
Contact
-
composition
Power supply
100 - 240 VACᜠ ± 10 % 50 / 60 Hz 24 VDCᜡ ± 10 %
Power
≤ 8 VA
consumption
Insulation
≥ 100 MΩ (500 VDCᜡ megger)
resistance
Dielectric strength
Between input terminal and power terminal: 2,000 VACᜠ 50 / 60 Hz for 1 min
0.75 mm double amplitude at frequency of 5 to 55 Hz (for 1 minute) in
Vibration
each X, Y, Z direction for 2 hours
Noise immunity
± 2 kV the square wave noise (pulse width: 1 ㎲) by the noise simulator
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Ambient
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
temperature
Ambient humidity
35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Mode Setting
→
Digital input
[▲] + [▼] 3 sec
→
Monitoring mode
[MODE]
RUN
→
Program mode
[MODE] 3 sec
→
[MODE] + [◀]
01) P 1-34, P2-30 Digital input key (HOLD: hold display value or ZERO: remote zero)
Monitoring Mode
• Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
• If any key is not entered for 30 sec in each parameter, it returns to RUN mode.
• [MODE] key: Saves current setting value and moves to the next parameter.
• [◀] key: Changes setting digits.
• [▲], [▼] key: Changes setting values.
Parameter
Display Defaults Setting range
1 CH output
M1-1
---- [Transmission output model]
value
OUt1
2 CH output
M1-2
value
OUt2
----
10)0 [Alarm output model]
M1-3
Alarm 1 value
AL1
M1-4
Alarm 2 value
AL2
00)0
M1-5
Alarm 3 value
AL3
10)0
M1-6
Alarm 4 value
AL4
00)0
Display max.
M1-7
---- Max. peak value in run mode
peak value
01)
hPEK
Display min.
M1-8
---- Min. peak value in run mode
peak value
01)
lPEK
01) Initial max. / min. peak value is saved after 2 sec from supplying the power.
Reset: Press the [▼] + [▲] keys for at least 1 sec
CN-640□-□
Pulse
Same with pulse input cycle
-
≈ 200 g (≈ 340 g)
Transmission
Alarm
(0 - 10 VDCᜡ)
≥ 10 kΩ
-
-
-
250 VACᜠ
5 A, 1a: 1 /
3 A, 1c: 2 /
5 A, 1a: 4 model
≤ 3 W
Auto
01)
[MODE] 3 sec
[MODE] 3 sec
Reset
[MODE]
• Displays output value by each
channel.
Temperature sensor input
: within temperature range
Analog input
: low-limit to high-limit scale
• Depending on the number of alarm
outputs, whether to display alarm 3 /
4 is different.
Program Mode
• Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
• If any key is not entered for 30 sec in each parameter, it returns to RUN mode.
• [MODE] key: Saves current setting value and moves to the next parameter.
• [◀] key: Changes setting digits.
• [▲], [▼] key: Changes setting values.
■ Universal input
Parameter
P1-1
Input type
Temperature
P1-2
unit
01)
P1-3
Display unit
Low-limit
P1-4
input value
High-limit
P1-5
input value
Decimal
P1-6
point
position
P1-7
Low-limit scale
P1-8
High-limit scale
P1-9
Input correction
Low-limit
value of
P1-10
transmission
output 1
High-limit
value of
P1-11
transmission
output 1
Low-limit
value of
P1-12
transmission
output 2
High-limit
value of
P1-13
transmission
output 2
Bar display
P1-14
CH
Low-limit
scale value of
P1-15
transmission
output 1
High-limit
scale value of
P1-16
transmission
output 1
Low-limit
→
scale value of
P1-17
transmission
output 2
→
High-limit
RUN
scale value of
P1-18
→
transmission
output 2
→
Input and
transmission
P1-19
output
extension
02)
Alarm 1
P1-20
operation
P1-21 Alarm 1 option
Display
condition
Alarm 2
P1-22
operation
P1-23 Alarm 2 option
-
Alarm 3
P1-24
operation
P1-25 Alarm 3 option
P1-20 to 27,
P2-19 to 26
Alarm 4
P1-26
operation
Alarm
operation /
P1-27 Alarm 4 option
option:
AT1.A,
AT2.A
Alarm output
P1-28
hysteresis
-
-
01) When changing the setting value, input type, high / low-limit scale, high / low-limit scale value of transmission
output 1 / 2, and AL1 to 4 are reset.
02) 0 mA, 0 VDCᜡ or less cannot be expanded. 1 VDCᜡ, 10 VDCᜡ input are available to extend only 5 %.
Display Defaults Setting range
aMA2 • Refer to Input Type and Range
IN-P
?C ℃, ℉
UNIT
?/O %, OFF, mV, V, mA, A, ℃, ℉
dUNT
0$00 Within input type range
L-RG
• Low-limit input value + 20 % F.S. <
High-limit input value
H-RG
2)00
0.0, 0.00, 0.000, 0
• Set the decimal point position of the
dP
)0
high / low-limit scale.
-1999 to 9999
L-SC
00)0
H-SC
10)0
000 -999 to 999
IN-B
[Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
0$00
[Transmission (0 - 10 VDCᜡ) output model]
lOR1
0 - 10 VDCᜡ
0)00
[Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
2)00
[Transmission (0 - 10 VDCᜡ) output model]
hOR1
0 - 10 VDCᜡ
1)00
[Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
0$00
[Transmission (0 - 10 VDCᜡ) output model]
lOR2
0 - 10 VDCᜡ
0)00
[Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
2)00
[Transmission (0 - 10 VDCᜡ) output model]
hOR2
0 - 10 VDCᜡ
1)00
[Transmission output model]
OUT1, OUT2
BAR
OUT1
lOU1
00)0
[Transmission output model]
hOU1
10)0
Temperature sensor input
: within temperature range
Analog input
: low-limit to high-limit scale
lOU2
00)0
hOU2
10)0
[Transmission output model]
5P: output DC 3.2 - 20.8 mA, 0 - 10.5 VDCᜡ
out of 5 % of analog input range
10P: output DC 2.4 - 21.6 mA, 0 - 11 VDCᜡ
ExIO
5P
out of 10 % of analog input range
0P: output DC 4 - 20 mA, 0 - 10 VDCᜡ in
the analog input range
[Alarm output model] □□□
AT1: high-limit alarm, AT2: low-limit
alarm, SBA: sensor break alarm, AT0:
no alarm output
[Alarm output model] ■
A: standard alarm, B: alarm latch,
□□□.■
AT!A
AL-1
C: standby sequence,
D: alarm latch and standby sequence
• Enter alarm option setting mode
: Operate in 'Alarm 1 operation' mode
select AT1 or AT2 and input [◀] key
□□□.■
AT@A
AL-2
[Alarm output model]
Same as 'P1-20 / 21 Alarm 1 operation
/ option'
□□□.■
AT!A
• Depending on the number of alarm
AL-3
outputs, whether to display alarm 3 /
4 is different.
□□□.■
AT@A
AL-4
[Alarm output model]
001 to 999
A-HY
001
Display
condition
-
P1-1 Input
type:
Temp.
sensor
P1-1 Input
type:
Analog
-
-
-
-
-
P1-37 User
level: HIGH
-
P1-1 Input
type:
Analog
&
P1-37
User level:
HIGH
-
-
-
P1-20 to 27
Alarm
operation
/ option:
AT1.A,
AT2.A