Quick Start Guide
4.0

Troubleshooting

If the device is not joined to the network after power up, verify the correct
configuration of the network ID and join key, and verify that Active Advertising
has been enabled on the Gateway. The network ID and join key in the device
must match the network ID and join key of the Gateway.
The network ID and join key may be obtained from the Gateway on the Setup >
Network > Settings page on the web server (see
network ID and join key may be changed in the wireless device by using the
following Fast Key sequence.
Table 2. Wireless Configuration Fast Key Sequence
Function
Wireless Configuration
Table 3
lists the Fast Key sequences for common transmitter functions.
Table 3. Rosemount WDM Special Fast Key Sequence
Function
Device Information
Guided Setup
Manual Setup
Wireless Configuration
Sensor Configuration
Sensor Calibration
5.0

Power module replacement

Expected black power module life is 10 years at reference conditions.
When module replacement is required perform the following procedure.
1. Remove the cover and module.
2. Replace the module (part number 701PBKKF) and cover.
3. Tighten to specification and verify operation.
5.1
Handling considerations
The black power module with the wireless unit contains two "C" size primary
lithium-thionyl chloride battery (black power module, model number
701PBKKF). Each battery contains approximately 5.0 grams of lithium. Under
normal conditions, the battery materials are self-contained and are not reactive
1. Reference conditions are 70 °F (21° C), transmit rate of once per minute, and routing data for three additional network
devices.
8
Fast Key sequence
2, 2, 1
Fast Key sequence
2, 2, 7
Configure Sensor, Join to Network, Config Advance
2, 1
2, 2
Temperature, Device Information, Power, Security
2, 2, 1
2, 2, 2, 5
Sensor Value, Sensor Status, Current Lower Trim,
3, 5, 2
Figure 5 on page
Menu items
Network ID, Join to Network, Broadcast Info
Menu items
Tag, Long Tag, Descriptor, Message, Date
Broadcasting, Calibrate Sensor
Wireless, Sensor, Display, HART, Device
Network ID, Join to Network, Broadcast Info
Sensor Data Sheet Values, Units, Serial Number
Current Upper Trim, Lower Sensor Trim, Upper
Sensor Trim, Device Variable Trim Reset
February 2019
7). The
(1)