Section 4: Settings

July 2021
Section 4: Settings
The following additional parameters become visible in the control unit for the Bettis RTS
electric actuator with the Modbus TCP option enabled.
Table 2.
P15.1
P15.2
P15.3
P15.4
P15.6
P15.7
P15.8
P15.9
P15.10
WARNING
!
After changing parameters P15.1 - P15.3, the protocol stack for the Modbus TCP is
restarted to apply the change.
WARNING
!
To allow the actuator to be unambiguously identified in the network, the MAC address is
displayed in the bottommost line of Status Area S5!
4
Installation, Operation and Maintenance Manual
Menu
Sub-menu
Poss. setting Notes/comments
item
item
0: inactive
1: fixed IP
Bus
Modbus TCP
2: DHCP
3: BOOTP
Bus
IP Address
0 to 125
Bus
Net Mask
0 to 125
Bus
Swap Bytes
Watchdog
0.0 – 10.0 s
Bus
time
(0): Standard
1: Analog
Bus
Sollwertquelle
2: Bus/analog
Bus
Status 2
Bus
Status 3
Bus
Status 4
Modbus TCP disabled.
The actuator has a fixed IP address (parameters P15.2 and
P15.3 have to be parametrised correctly).
The actuator receives its IP address from the DHCP server.
The actuator receives its IP address from the BOOTP server.
Valid IP address (only relevant if P15.1 is set to 1 (fixed IP))
Valid net mask (only relevant if P15.1 is set to 1 (fixed IP)).
0, 1
Swap the low and high bytes in registers.
Monitoring of the toggle bit transmitted from the master
(bit 7 in the command). With a bus watchdog time set, this
bit has to toggle within that time; otherwise there is a bus
(0.0 s)
watchdog fault. At 0.0 s the watchdog function is disabled,
in which case toggling of the toggle bit may be omitted.
The set point is specified via the Modbus TCP
(only relevant when the positioner is enabled).
The set point is specified by the analog signal
(only relevant when the positioner is enabled).
With an error-free bus, the set point is specified via the
Modbus TCP. With a bus error, the analog value is switched
to (only relevant when the positioner is enabled).
(0)
Standard assignment for Status 2.
1 - 2
Reserved for future use.
(0)
Standard assignment for Status 3 (current event).
1 - 2
Reserved for future use.
(0)
Standard assignment for Status 4 (current event).
1 - 2
Reserved for future use.
VCIOM-15517-EN Rev. 0

Settings