Também para Emerson FB1200: Manual de substituição de placas de terminação no terreno (18 páginas), Manual de substituição (18 páginas), Manual de substituição no terreno (14 páginas), Manual de substituição no terreno (8 páginas), Manual de substituição no terreno (8 páginas), Manual de substituição (8 páginas)

Emerson FB1200 Manual de substituição no terreno
Removing/Replacing Sensor Assemblies
DANGER
EXPLOSION HAZARD: To replace the sensor you must completely remove the flow computer
from its installation location and move it to a non-hazardous area. Ensure the area is non-
hazardous before disconnecting the flow computer.
CAUTION
MAY CAUSE INJURY TO PERSONNEL OR DAMAGE EQUIPMENT
Because I/O, ground, and other wires enter the flow computer through conduit fittings and then
connect to the boards inside, a qualified technician must disconnect all wiring coming into the
flow computer and pull it out through the conduit fittings in order to replace the sensor
assembly.
You must then reinstall all boards and modules and completely rewire the unit.
If not already done, be sure to label all wires before disconnecting so you can identify them later
during the rewiring process.
Field Replacement Kit Part Numbers
Refer to
correct field replacement kit part number.
Required Tools
Ambient Temperature Range
May be used up to a maximum ambient temperature of 80C and a minimum ambient
temperature of -40C; see end product data plate for ambient temperature.
Electrical Ratings
FB1100/FB1200 Flow Computer Sensor Assembly Field Replacement Guide
Table 1
(for FB1100) or
#1 Phillips-head screwdriver
#2 Phillips-head screwdriver
3/32-inch flat head screwdriver (for 3.81 mm pitch terminal block connections on FB1200
Flow Computer with additional I/O).
1/8-inch flat-hear screwdriver (for 5.08 mm pitch terminal block connections)
Hexagonal torque wrenches. Ranges must include 4 to 6 in-lbs (0.5 to 0.7 N-m), and 8 to
12 in-lbs (0.9 to 1.4 N-m).
2 mm hex wrench (for manipulating rotation set screws)
3 mm hex wrench (for end cap clamps)
Input Voltage: 5.7-30Vdc, 10 Watts Max
Table 2
(for FB1200) on pages
D301842X012
November 2020
iii
through
v
to determine the
1