Supported Commands
0x03 Read Multiple Registers
0x06 Write Single Register
0x16 Write Multiple Registers (for motor speeds only)
A request to use a function that is not available will return an illegal function exception.
Register Types
All registers are 16 bits wide with addresses using the standard MODICON protocol. Floating point values
use the standard IEEE 32-bit format occupying two contiguous 16 bit registers. ASCII values are stored with
two characters (bytes) per register in hexadecimal format.
Motor Operation Registers
Motor Speed
Motors are operated simply by sending the desired speed to each motor's speed register. Positive percent-
ages result in CW (forward) rotation while negative percentages result in CCW (reverse) rotation.
FORWARD: +60 to +100% | REVERSE: -60 to -100% | STOP: 0%
Speeds below 60% may result in a stalled motor and should not be used.
Included power supply is sufficient to drive a single motor at a time.
Driving multiple motors simultaneously may cause the power supply voltage to drop below acceptable
levels and put the pump into a fault protection mode requiring a power cycle.
To drive multiple motors reliably, provide 0.5A/Motor (2.1mm jack, center positive)
Motor Life
Motor life and service intervals can be tracked by observing the pump motors' accumulated run time which
is tracked in seconds in a 32-bit unsigned integer register for each pump motor.
Timeout
Timeout value (seconds) can be set to shut off all pumps in the even no communication is receieved from
the master device within a set period of time.