TROUBLE SHOOTING
PROBLEM
Outer ring on push button
not illuminated.
No water flow
Continuous water flow
CAUSE
No Power
Leads not connected correctly
No power
Faulty solenoid valve
Water or structural damage to
electrical components
Incorrect connections
Damage to sensor lead or power
supply lead
Pressure exceeding 500kPa
Water corroded electrical
connections
Solenoid valve jammed open
Solenoid installed
incorrectly
Version 2, 30 August 2017, Page 7 of 8
RECTIFICATION
Check power is reaching transformer
Ensure all leads are firmly pushed
into connectors
Check power is reaching transformer
Check electrical connections, replace
solenoid valve
Replace damaged electrical
components
Check all connections
Check and replace lead & controllers
Reduce pressure to solenoid to 350kPa
Replace electronic components
Remove obstruction from solenoid
valve
Reinstall valve correctly