Installation, Operation & Maintenance

Maintenance

Cleaning

Concentrations of alcohol found in many products may damage, deteriorate, or affect the gas sensing elements such as wine;
deodorants; stain removers and thinners. Other gases and substances to avoid are corrosives (i.e., chlorine & hydrogen chloride);
alkali metals; basic or acidic compounds; silicones; tetraethyl lead; halogens and halogenated compounds!
Keep your ParkSafe controller and detectors in good working order
Remove any dust/debris from the outer enclosures regularly using a slightly damp cloth.
Never use detergents or solvents to clean your device(s).
Never spray air fresheners, hair spray, paint or other aerosols near the detectors.
Never paint the device(s). Paint will seal vents and interfere with the equipment.

Manual Circuit Simulation Test

Access to the interior of the detector, when carrying out any work, must be conducted by a competent person!
This circuit test does not check the gas sensing element itself!
When the test button on the
to ensure all configured systems, outputs, alarms, indications, and other external devices operate as intended
in response to dangerous levels of gas.
When the button is released – the test sequence will terminate and return to normal operation.

Annual Service Message

The annual service message timer will begin after five (5) hours of continuous power irrespective of whether the system is then
used intermittently!
A service message will appear on the ParkSafe controller home screen after one year of any connected
ParkSafe detector operation. The detector will still operate during this time, but you should contact your
supplier immediately.
We recommend that the system is serviced/bump tested at least annually from the date of installation for
optimum performance and protection due to sensitivity drifts. Enter the status screens on the controller to
determine if the ParkSafe detector requires a [Service] or if it has reached its [End of Life].

End of Operational Life (EOL)

The EOL is approximate from the first five (5) hours of continuous power!
The EOL will depend on the type of gas your detector is targeting and may vary depending on its application and environmental
conditions such as the frequency of exposure to the target gas, poisons, or inhibitors!
At the end of their working life, electrochemical sensors for PARKSAFE detectors should be disposed of in an environmentally safe
manner. Alternatively, all detectors can be securely packaged and returned to AGS clearly marked for disposal.
Electrochemical sensors should not be incinerated as this may cause the cell to emit toxic fumes.
Enter the status screens on the controller to determine if the ParkSafe detector requires a [Service] or if it has
reached its [End of Life]. End of Life means the detector will need replacing and the Detector 'Fault' LED will
remain illuminated. The typical life of a ParkSafe detector depends on its application, environment and
intended target gas. In addition, the operational life may be prolonged if the equipment is installed and
maintained in accordance the instructions stated within this manual.