CAUTION:
Installation should be only performed by
technically competent personnel. Local Regulations
regarding electrical installation & safety must be observed.
The host equipment is required to provide a suitable
electrical, mechanical and fire enclosure to meet relevant
safety standards.
Impairment of protection will occur if the product is used in a
manner not specified by the manufacturer.
1. INSTALLATION
Installing Option Modules/Maintenance
1
/
Din Size Instruments
8
CPU PCB
Mounting Struts
Option Module A
Option Module 2
Option Module 3
Option Module 1
PSU PCB
CAUTION:
All power supply connections to the device must be
removed when carrying out any form of maintenance.
To access modules 1 or A, first detach the PSU and CPU boards from the front by
lifting first the upper, and then lower mounting struts. Gently separate the boards.
a.
Plug the required option modules into the correct connectors, as shown below.
b.
Locate the module tongues in the corresponding slot on the opposite board.
c.
Hold the main boards together while relocating back on the mounting struts.
d.
Replace the instrument by aligning the CPU and PSU boards with their guides
in the housing, then slowly push the instrument back into position.
Note: Option modules are automatically detected at power up.
Option Module Connectors
1
/
Din Size Instruments
8
Option Slot 2
Connector
PL4A
Option Slot 1
Connectors
PL7 & PL8
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
Panel-Mounting
The mounting panel must be rigid, and may be up to
6.0mm (0.25inch) thick. Cut-out sizes are:
Cut-Out Dim A
Cut-Out Dim B
1
1
/
Din = 92mm
/
Din = 45mm
8
8
A
For n multiple instruments mounted side-by-side, cut-out
1
A is 96n-4mm (
/
Din)
Tolerance +0.5, -0.0mm
8
Mounting Panel
Instrument
Housing
Ratchets
Gasket
Do not remove the panel gasket; it is a seal against dust and
CAUTION:
moisture.
Rear Terminal Wiring
connections to the device must be made through a spade format or similar
All
connection, with connection to the spade terminal touching both the
insulation and conductor material.(Use a standard crimping tool)
All connections must be Mechanically secured so as to prevent any wiring
becoming loose and coming in contact with other wires or the instrument
casing
The above applies to any and all connection to hazardous mains supply either
direct or indirect (Through a switch (Relay))
USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT)
Use Screened Cable on Retransmission Option 1
Single Strand wire gauge: Max 1.2mm (18SWG)
1
/
Din Size Instruments
8
B
This diagram shows all possible option combinations. The actual connections
required depend on the model and options fitted.
Check information label on housing for correct operating
CAUTION:
voltage before connecting supply to Power Input
Fuse: 90 – 264V ac – 1amp anti-surge
24/48V ac/dc – 315mA anti-surge
Electrical shock can result in death or serious
injury. Avoid contact with the leads and
terminals. High voltages that may be present
on leads can cause electrical shock
Slide mounting clamp
Note: At first power-up the message is displayed, as described
over the instrument
in section 3 of this manual. Access to other menus is denied until
housing towards rear face
configuration mode is completed
of mounting panel until
the tongues engage in
2. SELECT MODE
ratchets and instrument is
clamped in position.
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down
legend is shown for 1 second, followed by the legend for the current
Hold instrument firmly in
Press
or
to choose the required mode, then press
position (apply pressure
An unlock code is required to prevent unauthorised entry to Configuration, & Setup
to bezel only)
modes. Press
or
to enter the unlock code, then press
Mode
Legend
Set Value
for 1 sec
followed
by
Operator
Set Up
Configuration
Product Info
Calibration
Special
Note: Automatic return to Operator Mode after 2 minutes without key activity.
3. CONFIGURATION MODE
First select Configuration mode from Select mode (refer to section 2).
Press
to scroll through the parameters.
second after, the parameter legend is shown, followed by the current
Press
or
to set the required value. Press
accept the change, otherwise parameter will revert to previous value. To exit from
Configuration mode, hold down
and press
Note: Parameters displayed depend on how instrument has been configured.
Refer to user guide (available from your supplier) for further details. Parameters
marked * are repeated in Setup Mode.
Parameter
Legend
Set Value
for 1 sec
followed
by
Mode Default
Input
See following table for possible codes
Range/Type
Code Input Type &
Code
Range
B: 100 - 1824 ºC
L
F
bC
.
B: 211 - 3315 ºF
bF
NC
C: 0 - 2320 ºC
CC
NF
C: 32 - 4208 ºF
CF
rC
J: –200 - 1200 ºC
JC
rF
J: –328 - 2192 ºF
JF
SC
J: –128.8 - 537.7 ºC
j
C
SF
.
J: –199.9 - 999.9 ºF
j
F
tC
.
K: –240 - 1373 ºC
KC
tF
K: –400 - 2503 ºF
t
C
KF
.
k
C
K: –128.8 - 537.7 ºC
t
F
.
.
K: –199.9 - 999.9 ºF
K
F
P24C
.
L: 0 - 762 ºC
LC
P24F
LF
L: 32 - 1403 ºF
L: 0.0 - 537.7 ºC
L
C
PTC
.
Note: Decimal point shown in table indicates temperature resolution of 0.1°
Parameter
Legend
Set Value
for 1 sec
followed
by
Scale Range
Scale Range Lower Limit +100
Upper Limit
Scale Range
Lower Limit
Scale Range Upper Limit -100
=XXXX,
=XXX.X,
Decimal point
position
=XX.XX,
=X.XXX
*Multi-Point
Mm
Scaling
Alarm 1Type
High Alarm 1*
Low Alarm 1*
Alarm 1
Hysteresis*
Alarm 2Type
The
High Alarm 2*
and pressing
.
mode.
Low Alarm 2*
to enter.
Al 2 Hysteresis*
to proceed.
Output 1 Usage
Description
Default Unlock
Codes
Normal operation
None
Output 1 PV
Retransmit
Tailor settings for
Type
application
Configure instrument for
use
Retransmit OP
Instrument information
None
1 Scale
Calibrate Strain Gauge
maximum
input
Retransmit OP
1 Scale
Special
None
minimum
TxPSU 1 level
While this key is pressed, and up to 1
value.
to display
?
,press
, to return to Select mode.
Output 2A
Usage
Adjustment Range &
Default Value
Description
Enables or Disables
Defaulting of Values within
Mode
Output 2B
Usage
Display Strategy
Input Type &
Code Input Type &
Serial
Range
Range
Communication
L: 32.0 - 999.9
Pt100: –328 - 1472 ºF
PtF
s Protocol
ºF
N: 0 - 1399 ºC
Pt
C
Pt100: –128.8 - 537.7 ºC
.
Serial
N: 32 - 2551 ºF
Pt100: –199.9 - 999.9 ºF
Pt
F
.
Communication
R: 0 - 1759 ºC
0 - 20 mA DC
Bit Rate
R: 32 - 3198 ºF
4 - 20 mA DC
S: 0 - 1762 ºC
0 - 50 mV DC
S: 32 - 3204 ºF
.
10 - 50 mV DC
Comms
Address
T: –240 - 400 ºC
0 - 5 V DC
Comms Write
T: –400 - 752 ºF
1 - 5 V DC
T: –128.8 -
0 - 10 V DC
400 0 ºC
T: –199.9 -
2 - 10 V DC
752 0 ºF
PtRh20% vs.
40%:
-10mV-50mV
Logic Input
0 - 1850 ºC
Usage
PtRh20% vs
40%:
32 - 3362 ºF
Pt100: –199 -
800 ºC
Logic Input
State
Adjustment Range &
Default Value
Description
Config Lock
*Multi point scaling is visible on Non Temperature ranges only
Max (Lin =
1000)
4. SETUP MODE
to Range Maximum
Range Minimum to
Note: Configuration must be completed before adjusting Setup parameters.
Min (Lin =
0)
First select Setup mode from Select mode (refer to section 2). Press
through the parameters
legend is shown, then the current
(non-temperature ranges
To exit from Setup mode, hold down
only)
Note: Parameters displayed depends on how instrument has been configured.
Parameter
Enables or disables the
input multi-point scaling
feature
Process High Alarm
Mode Default
Process Low Alarm
No alarm
Alarm 1 value, adjustable within scaled
Max
range, in display units
Min
1 LSD to full span in display units on
safe side of alarm
Options as for alarm 1
Max
Min
Options as for alarm 1
Retransmit PV Output
0 to 10VDC (adjustable)
transmitter power supply*
0 to 5 V DC output
0 to 10 V DC output
2 to 10 V DC output
0 to 20 mA DC output
4 to 20 mA DC output
Display value between, -1999 & 99999
Range
max
at which Output 1 will be at maximum
Display value between, -1999 & 99999
Range
min
at which Output 1 will be at minimum
.
Output 1 Power Supply (0 to 10VDC)*
Alarm 1, direct, non-
latching
Alarm 1, reverse, non-
latching
Alarm 1, direct, latching
Alarm 1, reverse, latching
Alarm 2, direct, non-
latching
Alarm 2, reverse, non-
latching
Alarm 2, direct, latching
Alarm 2, reverse, latching
Logical Alarm 1 OR 2,
direct
Logical Alarm 1 OR 2,
reverse
Any active alarm, direct
Any active alarm, reverse
As for Output 2
Usage
, , , , or
(refer to section 8)
Modbus with no parity
Modbus with Even parity
Modbus with Odd parity
1.2 Kbps
2.4 Kbps
4.8 Kbps
9.6 Kbps
19.2 Kbps
1 to 255 (Modbus)
Read/Write
Read Only
Reset latched relay(s)
Initiate Tare (zero display)
Reset min/max PV values
Reset Alarm 1 elapsed
time
Reset Alarm 1 elapsed
time
& min/max PV values
Close contact activates
logic state
Open contact activates
logic state
Config Mode lock code, to
to scroll
(while this key is pressed, and for 1 sec after, the parameter
value). Press
or
to change the value.
and press
to return to Select mode.
Legend
Set
Adjustment Range &
Default Value
for 1
sec followed
Value
Description
by
Enables or Disables Defaulting
of Values within Mode