AGS Mini Merlin LPGCO v2-FL Instalação, operação e manutenção - Página 9

Procurar online ou descarregar pdf Instalação, operação e manutenção para Detectores de gás AGS Mini Merlin LPGCO v2-FL. AGS Mini Merlin LPGCO v2-FL 16 páginas. Dual gas detector

Mini Merlin Installation, Operation & Maintenance
Wiring – Pilot Water Heater & Boiler Limit Breaker
The device can be used to directly shut the pilot of a water heater in an alarm or power failure state using a product
from Field Controls. The BMS terminals may also be used to connect to a home alarm system.
Wiring – Remote Shut Off
When using this input, only the mains utility output shall de-energize. If you are using the CO or NG relay to shut down
a boilers external limit circuit, you will need to wire the input in series with the relay output.
Auto Reset & Buzzer Switches
In the event of a power loss – the mini-merlin will restart
automatically when power is restored.
The buzzer will sound every 15 seconds during pre-alarm
and continuously at alarm level.
This is the factory default condition.
Rev: 03 05-22
Your mini-merlin can be integrated with remote devices with an open /close circuit via
the Remote Shut-Off volt free switch terminal.
This terminal has a factory fitted link installed. This terminal is normally closed and will
alarm when energised open - isolating the gas supply.
ON
OFF
In the event of a power loss – the mini-merlin will need to
be reset manually when power is restored.
This is the factory default condition.
The buzzer will not sound at any gas level.
9