Installation, Operation & Maintenance
Main Board Connections
POWER/ LINE IN.
1.
110-120Vac mains power should be supplied to the [POWER/LINE IN] connector using a 3 core cable and fused at
3A. When mains power supplied to the panel - a red LED will illuminate located on the front cover.
OUTPUT 1 RELAY.
2.
This relay output switches when any external gas detectors reach 'pre-alarm' status and the [0-10V OUTPUT] will
send 5V to ventilation systems.
OUTPUT 2 RELAY.
This relay output switches when any external gas detectors reach 'alarm delay' status and the [0-10V OUTPUT] will
send 10V to ventilation systems.
ALARM RELAY.
This relay output switches when any external gas detectors reach 'alarm delay' status for longer than the selectable
5 - 25 minutes time following the [OUTPUT 2] relay.
DAMPER RELAY.
This relay output can switch together with either OUTPUT 1, OUTPUT 2 or ALARM relays - selectable in the settings
menu.
DETECTOR CHAIN.
3.
24vdc power and Modbus data is wired to Parksafe gas detectors [DETECTOR CHAIN] - [+ / - / D+ / D-].
Up to 16 detectors can be connected, chained in parallel up to approx. 500 yards from the panel depending on chain
configuration, wire type for power and condition. Connect detectors in a parallel (daisy chain) method.
Any other way may cause communication issues or damage to the overall system.
For MODBUS communications, a shielded and twisted pair cable is used. The shielding can be of 2 types: braided
[mesh of thin conducting wires] or foil (consisting of a thin sheet of metal covering the twisted wires).
If you are encountering noise or irregular problems with a Modbus link, the problem is likely related to grounding,
incorrect shielding or wiring mains power next to Modbus wiring.
For more information, refer to your Parksafe detector manual.
SOUNDER/ STROBE.
4.
This relay output (24VDC) is for an external sounder alarms/ strobe lighting to activate on alarm.
24VDC
.
5.
This is a permanent 24Vdc power output for external auxiliary devices. Max output: 200mA.
0-10V OUTPUT.
6.
This output can drive ventilation systems. Under normal operating conditions, this output can send either 0 or 2V –
selectable in the settings menu. The [0-10V OUTPUT] will send 5V when [OUTPUT 1] relay is activated and 10V
when [OUTPUT 2] relay is activated.