Mainpine EPC Manual de Instruções - Página 10

Procurar online ou descarregar pdf Manual de Instruções para Controlador Mainpine EPC. Mainpine EPC 16 páginas. Charging controller

5
CONNECTION
Depending on the device version the Mainpine EPC charging controller is connected to the EVSE in the following methods:
WARNING: UNDESIRABLE HEAT GENERATION OR FIRE DUE TO INADEQUATE
FUSING
The internal fuses are designed only to protect the device itself . The system installer and plant operator are responsible for the
necessary line protection .
The relay outputs are not fused within the device . Without appropriate protection of the relay outputs, overloading can cause
undesirable heat generation or even fire . The relay outputs are to be fused externally by the plant constructor .
WARNING: VIA THE PILOT SIGNAL, THE MAINPINE EPC CHARGING CONTROLLER
SPECIFIES THE MAXIMUM CHARGING CURRENT THAT CAN BE CALLED UP BY THE
VEHICLE.
This specified current must be consistent with the line protection configured for the charging device and the rest of
the plant configuration . Failure to observe this notice can result in injury to persons or property damage .
NOTICE
Connect the terminal (L/N) with the main last .
5.1 CONNECTING TERMINALS & TERMINAL ASSIGNMENT
TETHERED VERSION
10
.
"Tethered" means that the charging cable is permanently connected to the
EVSE .
P3-P6 are not present and relay 1 will energize for all charging currents . Thus,
the RCBO should be rated at the maximum current configuration of the EPC .