7. Start new measument with the device button

Some situations may require a re-measuring of
the dimmer, e.g. if the load is changed or the load
type is modified. To start programming, press and
hold the device button
After 20 sec. the programming mode starts (LED
and load turns off), each parameter is indicated
by a flashing of the LED and load for 2 seconds.
Select a parameter from below table.
Parameter Load / Function
1
any load
2
3 *
4
5
6
corridor mode
7
Reset
12
Manual
or push button
Features
Automatic calibration - the load type is determined automatically, dimming
parameters are set automatically and the dimming curve is adjusted to achie-
ve the best possible dimming result
reset to factory default settings
XRD600 REG
To activate, release the button within these 2 sec-
onds, a flashing pattern follows and the parameter
will be processed. If the button is released outside
this 2 sec. window, the programming will be ter-
.
minated.
Programming must be done within the
first 60min after power-on.
The key must be released within the active
phase for each parameter (as long as the
LED is on).
; Dimming curve (linear characteristic)
; Dimming curve (fixed LED curve) * Factory setting
; Dimming curve (automatic)
; Dimming curve (fixed)
To leave a set corridor mode, it is necessary to perform
a factory reset.