All flue connections must be sealed. Doors in the register plate must be present or a soot box
fitted in the back or side of the fireplace to enable access to clean the chimney when the stove
is installed without a flue liner. The installation of a flue liner is recommended.
If the chimney has been lined and cannot be swept through the stove an access door on the first
length of flue must be installed for cleaning access.
The Hembury 6 &8 model's requires a minimum of 150mm (6") liner.
Diagrams showing the flue outlet from the top (A), back (B) and back box (C).
X = Position of baffle plat
Y = Back protection brick
Please Note: All Profile top stoves use the 6mm black rope seal supplied under the flue spigot
to bring the flue spigot flush with the stove
Pre – Lighting Check and Commissioning
Check all Building Regulations have been adhered to.
The baffle plate is in the right position.
A smoke test has been done to check the chimney is clear.

Data Plate

All stoves are numbered and performance marked on a data plate which is found on a swinging
arm located at rear or base of the stove.

Air Vent

Under part J of building regulations an air vent of the appropriate size must be fitted for all
stoves with a kw rating of over 5kw.
Very air tight properties designed with air permeability less than or equal to 5.0 m3/ (h.m2) per
hour, an air vent will need to be fitted for all kilowatts.