Jaga RDG160 Instruções de utilização - Página 2

Procurar online ou descarregar pdf Instruções de utilização para Termostato Jaga RDG160. Jaga RDG160 2 páginas. Jaga room regulator with lcd screen

Room regulator with LCD screen
Control + Thermostat_control per room
/
Temporary timer for extended presence or absence
The Comfort and Energy Saving modes can be temporarily extended
temporary timer.
1. To set the temporary timer, press and hold the operating mode button for maximum 3 seconds.
While holding the button, turn the rotary knob clockwise or counterclockwise as required.
a) Turn the rotary knob cl ockwise to extend Comfort mode.
Display:
0....+9:30
b) Turn the rotary knob counterclockwise to extend Energy Saving mode.
Display:
0....-9:30
2. Release the operating mode button and the mode is temporarily changed, indicated by
After the temporary timer has elapsed, the thermostat
was active before:
Extended Comfort mode
New operating mode = Energy Saving
Extended Energy Saving mode
New operating mode = Comfort
If Energy Saving mode cannot be selected via the operating mode button (P02
will be used for extended absence instead!
The temporary timer function is abor ted whenever a new setting is made
Note:
Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active
To enable this function, the time for the extended period must be set via parameter P68.
Changing from heating to cooling mode
Depending on the type of plant, the changeover from heating to cooling (or vice
versa) is made either automatically by a changeover sensor or a remote
changeover switch, or manually by pressing the operating mode button (see
parameter P01)
To select cooling or heating manually (P01=2), press the operating mode button
until the desired mode appears
With automatic changeover or continuous heating / cooling, symbols
indicate that the system currently operates in heating or cooling mode
With manual changeover, symbol
operates in heating or cooling mode
Control parameters
If you want to change control parameters, proceed as follows:
1. Press both buttons simultaneously for at least 3 seconds.
2. Release them and, within 2 seconds, pr
ess the right button again for 3 seconds.
The display shows P01.
3. Select the required parameter by turning the rotary knob.
4. Press button
(OK). The current value of the selected parameter starts blinking and can be
changed by turning the rotary knob.
by 0.5 to 9.5 hours using the
.
will resume operation in the operating mode that
≠2), Protection mode
/
appears, indicating that the system currently
CODE: 8751.050006
If you want to change control parameters, proceed as follows:
1. Press both buttons simultaneously for at least 3 seconds.
2. Release them and, within 2 seconds, pr
The display shows P01.
3. Select the required parameter by turning the rotary knob.
4. Press button
(OK). The current value of the selected parameter starts blinking and can be
changed by turning the rotary knob.
5. Press button
(OK) to con rm the adjusted value, or
If you wish to adjust additional parameters, repeat steps 3 through 5, or press
parameter setting mode.
Parameter list
No.
Parameter name
P01
Control sequence
P02
Mode selection via operating
mode button
P03
Mode selection via fan mode
button
P04
Selection of °C or °F
P05
Sensor calibration
P06
Standard temperature display
P07
Additional display information
P08
Comfort basic setpoint
P09
Minimum setpoint limitation
in Comfort mode
P10
Maximum setpoint limitation
in Comfort mode
P11
Setpoint for heating in Energy
Saving mode (WheatE-saving)
P12
Setpoint for cooling in Energy
Saving mode (WcoolE-saving)
P13
Electrical heater in cooling
mode
P14
Button lock
The control parameters displayed depend on the DIP switch settings made
ess the right button again for 3 seconds.
(Esc) to cancel the change.
(Esc) to leave the
Default value
Setting range
2-pipe / 2-stage:
0 = heating only
1 = cooling only
1 = cooling only
2 = H/C changeover, manually
4-pipe:
3 = H/C changeover, auto
4 = H and C
4 = heating and cooling
1
1 = Comfort / Protection mode
2 = Comfort / Energy Saving /
Protection mode
0
0 = Auto / Manually
1 = Manually
2 = Auto / Manually /
Protection mode
0
0 = °C
1 = °F
0.0 K
– 3...3 K
0
0 = room temperature
1 = setpoint
0
0 = --- (no display)
1 = C and F
21 °C
5...40 °C
5 °C
5...40 °C
35 °C
5...40 °C
15 °C
OFF, 5 °C...WcoolE-saving
30 °C
OFF, WheatE-saving...40°C
ON
OFF = disabled
ON = enabled
0
0 = disabled
1 = automatically
2 = manually
Adj.