Gree TDmetal Modbus Gateway Manual de instalação - Página 8

Procurar online ou descarregar pdf Manual de instalação para Porta de entrada Gree TDmetal Modbus Gateway. Gree TDmetal Modbus Gateway 12 páginas. For u-match r32 units

Gree TDmetal Modbus Gateway Manual de instalação

Con guration by wired controller

3 Con guration by wired controller
For activation of Modbus communication and address settings of indoor unit, you will
need wired controller XK117 (Z4K351GJ)

3.1 Activation of Modbus communication

In default settings, the unit is ready to communicate with central controller, it is required
to activate it for Modbus communication.
1. Under OFF state, hold buttons
2. Press MODE multiple times to get to
FUNCTION and TIMER for more than 5
10th settings parameter (middle number),
seconds.
by arrows choose option 01 and con rm
by pressing SWING/ENTER button.

3.2 Address settings of indoor unit

When there are several Modbus Gateways on the common bus, each indoor unit has
to be assigned with unique address. Otherwise it is recommended to keep the default
address 1.
1. Under OFF state, hold buttons FUNCTION
2. By arrows choose unit's address and
and MODE for more than 5 seconds.
con rm by pressing SWING/ENTER button.
8 Modbus Gateway