Decagon Devices GS3 Manual - Página 5

Procurar online ou descarregar pdf Manual para Acessórios Decagon Devices GS3. Decagon Devices GS3 12 páginas. Greenhouse sensor

GS3 Integrator Guide
R34

SDI-12 COMMUNICATION

SDI-12 is a common bus communication protocol that allows you to connect multiple sensors to a
common data line. The SDI-12 protocol requires a unique alpha numeric sensor address for each sensor
on the bus so that a data logger can send and receive readings to specific sensors.
Visit
www.sdi-12.org
to download the latest SDI-12 Specification or find out more information about the
standard.
DECAGON'S SDI-12 IMPLEMENTATION
Decagon's sensors use a low impedance variant of the SDI-12 standard sensor circuit (see the Equivalent
Circuit Diagram). This allows for up to 62 sensors to be connected onto the bus at one time instead of the
10 that is stated in the standard. Keep in mind that the more sensors you have on a bus, the more
difficult it will be to isolate and remove the faulty sensor and restore communication to the remaining
sensors on your SDI-12 bus.
Out of the factory, all Decagon sensors start with SDI-12 address zero and print out the DDI-Serial string
during the power up time specified in the Electrical and Timing Characteristics section (See the start up
sequence diagram in the DDI-Serial section for a detailed diagram). This can be interpreted by non-
Decagon SDI-12 sensors as a pseudo-break condition followed by a random series of bits. To circumvent
this issue, GS3 sensors with firmware version 3.37 and newer omit the DDI-Serial string when their SDI-12
address is non-zero. Simply changing the sensor addresses on the SDI-12 bus to non-zero values will
prevent any race conditions on the data line during sensor power up.
After the power up time, our sensors are fully compatible with all the commands listed in the SDI-12
Specification v1.3 except for the continuous measurement commands (aR0 – aR9 and aRC0 – aRC9).
SENSOR BUS CONSIDERATIONS
An SDI-12 bus isn't something you can set up and just walk away. Sensor buses require regular checking,
sensor upkeep, and sensor trouble-shooting. If one sensor goes down, that may take down the whole bus
even if the remaining sensors are functioning normally. Power cycling the SDI-12 bus when a sensor is
failing is okay but we do not recommend scheduling power cycling events on an SDI-12 bus more than
once or twice a day.
Many factors influence the effectiveness of your bus configuration and many questions should be
answered: How often should data be checked? How is the data delivered to the end user? How do I isolate
a faulty sensor?
Visit our website and read our application note and view our virtual seminars on Best Practices for SDI-12
Sensor Networks.
For support contact us via email at
5
or call us at 1.509.332.5600 between 7AM to 5PM PST