Figure 3: Wiring Connection for Devices Without Current
The optional 100 uF capacitor shown in parallel with the R
duces measurement noise. It should have a voltage rating higher
than the largest supply voltage. Be sure to observe correct polarity.
The MAS-1 requires a voltage of at least 12 V. This limits the value
of R
olt since part of the total voltage drop will be across the re-
V
sistor. Equation 2 can be used to determine the maximum value for
R
olt. Table 1 shows time resistance values.
V
Table 1: Maximum resistance values for R
The MAS-1 sensor has several advantages over voltage-output sen-
sors, even for voltage-input data loggers.
1. The MAS-1 supply voltage does not need to be regulated for
the sensor to work properly; it can be any value between 12
and 32 volts, without affecting sensor output.
2. When using a current-based sensor like the MAS-1, the signal
is not affected by electrical resistance in the cable, so the sensor
output is not affected by cable length or wire gauge.
3 INTEGRATING THE MAS-1
V
12 = 0.02R
supply
Supply Voltage
13 V
24 V
32 V
7
V oltM ax
at specified voltages
V olt
Load
50 ohms
600 ohms
1000 ohms
re-
V olt
(2)