9.1 SERVICE OUTPUT
SERVICE is Programmable from the Installer Manual by using parameter P02:
P02 = 0 DISABLED: the output does not work.
P02 = 1 THERMOSTAT: the output is activated if the temperature of S1 probe is above Thermostat E07
P02 = 2 GRILL: press for 3 seconds K3 key to turn on/off the output
P02 = 3 AIR DAMPER: this output is used to manage an Air Damper to adjust for Combustion Air Flow
9.2 AIR DAMPER
To make use of the Air Damper function set parameter P02 = 3
If the output is ON the Air Damper will be Open, if the output OFF the Air Damper will be closed.
The Air Damper will stay Open as long as the temperature of S1 probe is below E06 Thermostat. The Air Damper
will close when the temperature is above this Thermostat.
If P12 = 1 the Start Manual function is enabled:
If S1 Temperature is below E05, the Air Damper will Close. During the Ignition phase of the Fireplace, by pressing
K3 key, the Air Damper will Open manually (the output corresponding Led will flash). When the Temperature falls
below E05, Thermostat after t06 time the Air Damper will close automatically.
9.3 S2 INPUT CONFIGURATION
Parameter P01 can be enabled to mange the following:
P01 = 0, input S3 = DISABLED
P01 = 1, input S3 = AMBIENT PROBE
P01 = 2, input S3 = AMBIENT THERMOSTAT
9.4 PROBE SENSOR/ AMBIENT THERMOSTAT
With the parameter P01 it is possible to enable the managing of the della Sonda/Termostato AMBIENT
Probe/thermostat.
If the Temperature of the Ambient Probe is above the thermostat b01 or the Contact of the External Ambient
Thermostat is Open (the Led flashes)
The Fan is Off
The Air Shutter is Closed
9.5 FAN ACCELERATOR FUNCTION
It allows the Fan to work at Maximum Speed, during a programmable time(t08), every time the fan is powered on.
Once the time has elapsed, the Fan will work at the programmed speed.
In order to disable the Accelerator Function, set the time t08 at 0 seconds.