MOUNTING
Mounting
DUPLEXVENT DV145SE has to be mounted in a place where
temperaturedoes not go below +10 °C. Without protective enclosure,
the unit must be located in a place with no acoustic disturbance:
storerooms, technical rooms etc.
Wall mounting
DUPLEXVENT DV145SE is mounted on the wall with a mounting
plate asshown in the adjacent fi gure. Make sure that the unit is
horizontally level after mounting.
Wall construction
Observe the wall construction during mounting. Avoid mounting the
unit on a hollow, echoing dividing wall and on a bedroom wall
because of sound conduction, or prevent sound conduction.
Condensing water connections
The delivery includes a water seal. By connecting a pipe to the water
seal the water condensing from extract air can be led to a fl oor
drain (not directly to the drain). The pipe must not rise after the water
seal. The unit has to be mounted horizontally level, so that condens-
ing water can get freely out of the unit.
Base (option)
Ø22
Ø 8
685
625
30
655
© Air ow • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
DV145SE
The minimum distance between the top of the unit and the
fi nished ceiling surface is 30 mm.
Pipe outer diameter ø 12 mm
Threaded bar M8x35
Shorter thread up
Length of adjusting screw
thread 37 mm
579
Take into account that the unit
rises during mounting 10 mm
higher than the fi nal height.
Bottom edge of wall bracket
Adjust the base with adjusting legs to make it straight.
Remove the (4) rubber plugs at the bottom of the unit.
Put the unit on top of the base so that the bars of the base
fi t in the holes at the bottom of the unit.
5