Major tech MT472 Manual de instruções - Página 8

Procurar online ou descarregar pdf Manual de instruções para Equipamento de teste Major tech MT472. Major tech MT472 12 páginas. 690v voltage tester

Major tech MT472 Manual de instruções

5. OPERATION

5.1. Function test / Self test

Ÿ Test the voltage tester on a known source.
Ÿ The voltage testers may no longer be used if one or several functions
fails or if no functional reliability can be detected.
Ÿ The instruments are equipped with an internal load enabling the tripping
of an RCD protection device of 10mA or 30mA.
Ÿ For voltage tests (L towards PE) in systems with RCD devices, the RCD
may be triggered. To avoid RCD tripping first test between L and N
(approx. 5s). Immediately afterwards testing L towards PE can be
carried out without RCD tripping.

5.2. Voltage Test

Ÿ Connect both test probes with power source.
Ÿ As from a voltage of >6V the voltage tester switches on automatically.
Ÿ The voltage is displayed via LEDs.
Ÿ For AC voltages "-" LEDs are illuminated.
Ÿ The instruments are equipped with an LED row comprising: ±12, 24, 36,
50, 120, 230, 400, 690V AC/DC. For DC voltage, the polarity of the
voltage displayed refers to the instrument test probe (+).
Ÿ Due to technical reasons the instrument cannot effectuate an automatic
switch-on for DC voltages within the range of approx. 0V to –/+4.5V.

5.3. Low impedance Test

Without pressing both low impedance buttons, the following voltage steps
(AC or DC) can be indicated: ±24, 36, 50, 120, 230, 400, 690V AC/DC. By
pressing both low impedance push buttons the voltage tester switches to
a lower internal resistance (suppression of inductive and capacitive
voltages). Thus, the indication of low impedance (5) is also activated. The
duration of the test with a lower internal resistance of the device (load
test) depends on the value of the voltage to be measured. To prevent
excessive warming of the voltage tester, it is equipped with a thermal
protection.

5.4. Voltage Test with RCD Trip Test

During voltage tests in systems equipped with RCD circuit breakers, a
RCD switch can be tripped at a nominal residual current of 10mA or 30mA
by measuring the voltage between L and PE.
8
7