VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions

Control Device

Check the alarm function
Short the sensor input with a paper clip or
similar, alternatively connect the sensor
and dip the electrode in water. Within
about 30 seconds, the buzzer sounds in
the receiver and the red LED will flash.
Press the button on the receiver -> sound
is muted. Remove the short circuit, alter-
natively, take the transmitter out of the
water. The red LED should go off within 30
seconds. Testing the alarm function is OK.
Press here.
Range Test
Before assembly it must be tested on the
location of the receiver can receive the
radio signal from the transmitter. Place the
receiver at the desired location and con-
nect the AC adapter. Place the transmit-
ter module in place in the well during the
"cap". Remove the battery from the battery
holder.
Subject to design modifications.
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se
Hold down the button and insert the battery.
When both LEDs are lit for about 1 second
at the same time, release the button now.
Both LEDs show flashing, 10 seconds in
between. After about 10 minutes a return to
normal operation.
If necessary, move the receiver unit to a
location where the transmitter's signal can
be received safely.
External connection
VA-Alert W/R
+ -
12 VDC
NOTE! There are many things that can in-
terfere with the radio signal. For example,
cars and bicycles placed between trans-
mitters and receivers can adversely affect
the signal. Therefore, it is very important
that the same conditions also apply after
range tests.
NO
C
NC
Relay
output