TROUBLESHOOTING
1) Power On light is not lit
Ensure the unit is receiving power (unit is wired correctly or plugged into an
-
active AC outlet)
If wired into the HVAC control panel, HVAC unit must be running
-
Ensure Display Panel door is closed completely
-
2) UV Lamp On light is not lit
Check that the lamp socket is firmly attached to the lamp base pins
-
Ensure the wires to the lamp socket have not become dislodged
-
Ensure the UV lamp is operational (open the Display Panel door; pull the UV
-
lamp out slightly so that the lamp glass can be seen; deactivate the "kill
switch" by depressing the kill switch button; if UV lamp does not light, replace
lamp – UV resistant safety glasses should be worn for this test)
WARNINGS
WARNING
Electrical Shock – The PCO/UV N-Duct™ system is to be wired or plugged into 110 –
240 VAC electrical power.
Ultraviolet Light is Harmful – Never look at a lit ultraviolet lamp without UV protective
glasses and skin coverings. Unplug the lamp before servicing.
Ultraviolet Lamp May Cause Injury – Ultraviolet lamps are made of glass and
therefore somewhat fragile. Safety glasses and gloves should be worn when handling a
UV lamp. In addition, UV lamps can be very hot and cause skin burns. Allow lamp to cool
before handling.
ULTRAVIOLET LAMP LIFE
Like all light bulbs, UV lamps have a life span. Unlike regular light bulbs, however, UV lamps
loose their effectiveness over time. Typically, after 9000 hours of use (approximately 1 yr.),
the lamps do not produce enough ultraviolet germicidal irradiation to be effective. However,
even after this time, the lamps usually do not burn out, but stay lit. This is often confusing
to owners, but the lamps simply no longer produce the intensity necessary to be effective in
improving or maintaining indoor air quality and must be replaced. It should also be noted
that some ultraviolet lamps burn out prematurely and do not last the full 9000 guaranteed
hours. AirGorilla' s visual and audible reminders of when the UV lamps need to be replaced
(or if they have burned out) help ensure you are receiving the full benefit and effectiveness
of the PCO/UV N-Duct' s™ advanced air cleaning technologies.