Replacement routines
Installing the new system board
Ê Insert the system board by holding it at a slight angle.
Ê Carefully shift the system board to the rear of the server until the connectors
engage with the cut-outs in the connector panel.
Ê Lower the system board carefully into the housing.
Ê Adjust the system board. If necessary adjust the position of the system
board with a gentle twisting motion.
I
When the system board is in the right position, the centre rings (see
red circles in
Ê Fasten the system board with the seven screws (see blue circles in
figure
20).
Ê Reinstall the spacer screw (see
Ê Reinstall the fan box and fasten it with the two screws (see circles in
figure
19).
Ê Reinstall all fan units (description see the Operating Manual).
Ê Reconnect all cables to the system board (see the cabling plans in the
Appendix of the Options Guide).
Ê If available, reinstall the TPM (see the
page
30).
Ê If available, reinstall the UFM (see the
page
32).
Ê Reinstall the riser card holders (see the Options Guide).
Ê Reinstall the CPU heat sinks (see the Options Guide).
Ê Reinstall the memory modules (see the Options Guide).
Ê Reinstall the air duct (see the
Ê Close the server and connect all power plugs (for a detailed description see
the Options Guide).
Ê Reconnect all external cables.
42
figure
20) engage with the holes indicated.
figure
section "Installing the air duct" on page
Service Supplement
18).
section "Replacing the TPM" on
section "Replacing the UFM" on
26).