Fujitsu ETERNUS DX60 S3 Manual de Planeamento do Sítio - Página 32
Procurar online ou descarregar pdf Manual de Planeamento do Sítio para Armazenamento Fujitsu ETERNUS DX60 S3. Fujitsu ETERNUS DX60 S3 41 páginas. Hybrid storage systems, all-flash arrays, power synchronized unit
Também para Fujitsu ETERNUS DX60 S3: Manual de configuração Ligação do servidor (12 páginas), Manual de configuração (28 páginas), Manual de configuração (13 páginas), Precauções de segurança (12 páginas)
Chapter 2
Rack Installation Specifications
This chapter explains the rack installation specifications of the ETERNUS DX.
2.1
Rack Installation Requirements
This section explains the requirements for installing the ETERNUS DX in a 19-inch rack.
2.1.1
Placement in the Rack
Note the following when installing the ETERNUS DX in the rack.
The center of gravity must be taken into consideration to prevent a rack from toppling over. Enclosures
•
should generally be installed from bottom to top to lower the center of gravity and to ensure the safe use
of racks.
Enclosures are installed in the following order (from bottom to top).
•
Table 2.1 Enclosure Installation Order
Installation order
4
3
2
1
*1: This is an Uninterruptible Power Supply.
*2: This is an optional product for only the ETERNUS DX.
When determining the rack-mounting layout of each enclosure and power distribution unit, consider the
•
length of each cable. For example, if the ETERNUS DX is installed at the top of a 2000mm rack and a 4m
power cord is used, the surplus length of the power cord at the bottom of a rack should be about 2m.
If the storage system is installed at the bottom of a rack, a space for the surplus of cables may not be
•
available in some racks, preventing the storage system from being pulled out when maintenance work
is required.
In this case, secure a space of 1U or more at the bottom when installing the storage system.
Enclosure
Drive enclosure
Controller enclosure
Power distribution unit
Power synchronized unit (*2)
UPS (*1)
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
32
Size (height)
2U
2U
1U/2U
1U
—
P3AM-8982-03ENZ0