The operator should perform all of the prestart checks.
Start the generator set according to the starting
procedure in the controller section of this manual. While
the
generator
set
is
smooth-running engine and visually inspect the
generator set for fluid or exhaust leaks.
2.4 Operation in Cold Weather
Climates
Cold weather operation is generally considered ambient
temperatures below freezing 0_C (32_F). The following
items are recommended for cold weather starting and/or
operation. Have a licensed electrician install 120 VAC,
15 amp outlets as needed if not already in the immediate
area.
Refer to the engine operation manual regarding engine
oil viscosity, fuel composition, and coolant mixture
recommendations.
An engine block heater is generally recommended
D
for most units when operated below 0_C (32_F).
Heater tape is recommended when the generator set
D
is operated at or below 50% of rated load. Wrap the
UL/CSA compliant heater tape around the crankcase
canister/breather system hose that runs from the
crankcase to the air intake and use cable ties as
needed to secure the heater tape. If the heater tape is
within 152 mm (6 in.) of the exhaust system, use
thermal insulation material to protect the heater tape.
14
Section 2 Operation
operating,
listen
for
2.5 Advanced Digital Control
Operation
a
Figure 2-3 illustrates the user interface on the Advanced
Digital Control (ADC 2100).
Note: Have setup and adjustments of the ADC 2100
performed only by an authorized Kohler
distributor/dealer. The setup and adjustments
are password protected.
4
1. LED display
2. Up and down arrow buttons (use for setup and
adjustment only)
3. Generator set master switch
4. Select button (use for setup and adjustment only)
Figure 2-3 ADC 2100 Control
2.5.1
Controls and Indicators
Figure 2-4 describes the controls and indicators located
on the controller. The LED display indicates generator set
status as shown in Figure 2-4. The display is activated by
a start or run command and remains active until the
generator set master switch is moved to the OFF/RESET
position or the power to the controller is removed.
The buttons on the controller keypad are used only for
system configuration and adjustment. The controller is
factory-set and should not require configuration or
adjustment under normal operating conditions. If the
generator set is reconnected to a different voltage
and/or frequency, refer to an authorized Kohler
distributor/dealer
adjustment instructions.
2
1
3
for
system
configuration
TP-6551 2/14
GM28707A-C
and