Generator Set
Note: See Section 1.10.2, Cable Specifications for
maximum cable lengths.
* RXT transfer switch with standard or combined interface/load
management board. Do not use a load shed kit with a
combined interface board.
1. Generator set terminal block. See Figure 3-5 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
Figure 1-24 Accessory Module Communication Connection Details
26
Section 1 Installation
1
GND
3
4
COM
COM
12 VDC
PWR
PWR
B
B
RBUS
A
A
TB3
2
3
A
B
PWR
COM
6
4
RXT*
A
B
PWR
COM
5
A
B
PWR
COM
Load Shed Kit
A
B
PWR
COM
A
B
PWR
COM
PIM
TP-6984