1.11.2 Carburetor Heater

An optional carburetor heater is recommended for
improved cold starting in locations where the ambient
temperature drops below 0_C (32_F). The carburetor
heater prevents condensation and carburetor icing. The
heater turns on when the temperature at the thermostat
falls below approximately 4_C (40_F) and turns off when
the temperature rises above approximately 16_C
(60_F).
The carburetor heaters are shown in
Figure 1-26.
To install the carburetor heater, follow the instructions
provided with the kit. Figure 1-27 shows the installed
carburetor heater kit installed for a 14 kW generator set.
Figure 1-28 shows the location for the carburetor heater
kit on a 20 kW generator set.
The heater thermostat is installed in the cord.
Figure 1-26 shows the location of the thermostat on the
power cord. The heater power cord and thermostat are
located in the generator set housing air intake area/
battery compartment.
Note: Do not place the heater thermostat inside the
generator set engine compartment.
thermostat must be exposed to the ambient air.
The heater requires a continuous source of power. Plug
the carburetor heater into one of the 120 VAC
receptacles provided.
1
2
14RES/RESL Carburetor Heater
1
2
20RES/RESL Carburetor Heater
1. Power plug
2. Thermostat
3. Heater
Figure 1-26 Carburetor Heaters
TP-6733 8/11
1. Carburetor heater (air cleaner removed to show heater)
2. Carburetor heater power cord
The
Figure 1-27 14RES/RESL Carburetor Heater
3
GM19463
1. Carburetor heater location
3
Figure 1-28 20RES/RESL Carburetor Heater
GM57968
2
1
Location on Engine (bulkhead removed
to show heater location)
Section 1 Installation
tp6195
1
tp6514
29