1.11 Prestart Installation Check

Review the entire installation section. Inspect all wiring
and connections to verify that the generator set is
ready for operation. Check all items in the following
Prestart Checklist.
Air Cleaner. Check that a clean air cleaner element is
installed to prevent unfiltered air from entering the
engine. See the generator set operation manual for
instructions.
Air Inlets.
Check for clean and unobstructed air
inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Enclosure.
Check that all enclosure panels and
internal baffling are in place.
Exhaust System.
Check for exhaust leaks and
blockages. Check the muffler condition.
• Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust
system connections.
• Check for corroded or broken metal parts and
replace them as needed.
• Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over,
the full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near
the generator set.
TP-6842 7/15

1.12 Set the Exerciser

Set the exerciser to automatically run the generator set
on the desired day and time every week or every two
weeks. See the generator set Operation Manual for
detailed descriptions of the unloaded and loaded
exercise operation.
When power is applied to the VSC controller (when the
battery or the AC power for the battery charger is
connected), you will be prompted to set the date and
time, and then to set the exerciser.
The first setting will flash. Press the Up and Down
arrow buttons to change the setting. Press Select to
save the setting and move on to the next. Repeat until
the date, time, and exercise are set and the controller
display shows the main menu. See the generator set
Operation Manual for more detailed instructions to set
the date and time and set the exerciser.
Press AUTO to place the generator set controller into
automatic mode.
Figure 1-23
Date:
05Dec2011
Time:
08:31am
Next Exercise:
08:31a 12Dec2011
Figure 1-22 Set Time, Date, and Exercise (VSC)
Setting will flash.
Press the up and down arrow
buttons to change the setting.
Press Select to save the
setting.
KPS_044
Section 1 Installation
23