5.1 LED indicator lights
The five LED lights indicate the status of power, communication, and temperature as well as operation states and faults. Use
the LED lights to determine the charge state and troubleshoot the battery charger.
voltage output state LEDRED voltage output state
LEDTemperature LEDCommunication LEDPower
Figure 4
LED Indicator Lights
Indicator
Indicator State
Power
Off
Steady On
Communication
Off
Steady
Blinking
Temperature
Off
Compensation
Steady
Blinking
Output Voltage
Blink Red
Blink Red
Blink Red
Steady Red
Steady Red & Green
Steady Green
Alternating Green & Red
Red and Green Off
Steady Green
Red and Green Blinking
Figure 5
LED Indications
22
LED
GM87448-
Description
AC not connected / Fuse open
Power is acceptable
No communication since power on self-test (POST)
Communication established and nominal
Temperature compensated output active
Temperature compensation warning due to intermittent or out of range signal
Under Voltage / Recovery State
Over Voltage
Bulk charge state
Absorption state
Float / Maintenance state
Equalize state
Battery connection reversed
Absorption timeout
Power On Self-Test (POST)
1
1
2
3
4
5
Intermittent or loss of communication after communication has
previously been established
CAN fault (collision, self-removal from CAN bus as defined by
applicable protocol definition)
CAN detected since last power on self-test (POST)
Temperature sensor not connected
Turned off by controller
Battery is not connected
Output failure with battery connected
Blown or open fuse
Shorted Output Leads
GM87448G
M94439-
TP-7077