8. CONNECTION WITH GATEWAY

Monitor measures each pulse in the fence system and sends the values to the Gateway every
15 minutes. If a voltage lower than the set limit is measured , data is sent to the Gateway
immediately and an alarm is triggered.
Setting the low voltage alarm level on the fence system
The 3 kV limit is set at the factory. The user can freely adjust this value in the Gateway (see
instructions for the Gateway). If the alarm limit on the Gateway is changed, it will not take
effect in the Monitor until the next time new data is received, i.e. in a 15 min cycle.
Low battery alarm
The Monitor's low battery is indicated on the Gateway when it drops below 10%.
We recommend replacing it within 2 weeks at the latest.
Display of the paired Monitor on the Gateway and all available information about
a specific device.
DETAILED SCREEN
Type of device
1
2
Time since last data transfer
3
Monitor battery voltage status [%]
4
Current set value for triggering an alarm [kV]
5
Fence voltage value [kV]
6
Signal level between Monitor and Gateway
8