IV. Conversion Module Wiring Diagram
The following diagram shows the connections from the existing B825-016 swing-arm, through the conversion module, 1492
cable and to the 1756-IB16 input module. The diagram can be used as an aid in possible system troubleshooting.
WARNING
+
-
B825-016 Swing Arm
Conversion Module Installation and Application Considerations
The input delay times for the B825-016 module versus 1756-IB16 module are as follows:
a) Off-to-On Delay
b) On-to-Off Delay
Refer to your B825-016 and 1756-IB16 Installation Manual wiring schematics and diagrams for more details.
10000021883 (Version 00)
There are several key application considerations and system specifications (bottom of drawing) when using
these components (conversion module, cable and output module). Read and understand these consider-
ations before installation.
Conversion: B825-016 to 1756-IB16 with 1492-CM800-LD008
1492-CM800-LD008
Common
9
Common
10
Input 1
1
Input 2
2
Input 3
3
Input 4
4
Input 5
5
Input 6
6
Input 7
7
Input 8
8
Input 9
11
Input 10
12
Input 11
13
Input 12
14
Input 13
15
Input 14
16
Input 15
17
Input 16
18
Common
19
+24 VDC
20
B825-016
2.5ms (typical), 11ms (max)
2.5ms (typical), 11ms (max)
1492-CABLE003X
1
Black
2
White
3
Red
4
Green
5
Orange
6
Blue
7
White/Black
8
Red/Black
9
Green/Black
10
Orange/Black
11
Blue/Black
12
Black/White
13
Red/White
14
Green/White
15
Blue/White
16
Black/Red
17
White/Red
18
Orange/Red
19
Blue/Red
20
Red/Green
1756-IB16
1ms (plus selectable filter)
2ms (plus selectable filter)
[Reference Doc: 41170-758 (Version 03)]
(2)
1756-IB16
10
GND-0
9
GND-0
1
IN-0
2
IN-1
3
IN-2
4
IN-3
5
IN-4
6
IN-5
7
IN-6
8
IN-7
11
IN-8
12
IN-9
13
IN-10
14
IN-11
15
IN-12
16
IN-13
17
IN-14
18
IN-15
20
GND-1
19
GND-1