ArmorPoint 24V dc Input Modules, Series A
ArmorPoint Digital Input Modules
Input Delay Time, ON to OFF
Input Point Density
Field Power Bus Supply
Voltage Range,
Nominal
Keyswitch Position
General Specifications
LED Indicators
PointBus Current, Maximum
Power Dissipation, Maximum
Thermal Dissipation, Maximum
Isolation Voltage
(continuous-voltage withstand rating)
Dimensions (includes I/O module
and mounting base)
Operating Temperature
Storage Temperature
Relative Humidity
Shock
Vibration
ESD Immunity
Radiated RF Immunity
EFT/B Immunity
Surge Transient Immunity
Conducted RF Immunity
Publication 1738-IN002B-EN-E - November 2004
0.5 ms hardware + (0-63 ms selectable
2, 4, or 8
10-28.8V dc
24V dc
1
2, 4, or 8 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
75 mA @ 5V dc
1738-IB2 - 0.7W @ 28.8V dc
1738-IB4 and -IV4 - 1.0W @ 28.8V dc
1738-IB8 and -IV8 - 1.6W @ 28.8V dc
1738-IB2 - 2.4 BTU/hr. @ 28.8V dc
1738-IB4 and -IV4 - 3.4 BTU/hr. @ 28.8V dc
1738-IB8 and -IV8 - 5.5 BTU/hr. @ 28.8V dc
50V rms
Tested at 1250V ac rms for 60s
Inches
4.72H x 2.83W x 1.65D
(Millimeters)
(120H x 72W x 42D)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing
IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
IEC 61000-4-4:
±3kV at 5kHz on signal ports
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz