CP Electronics ALC-PRM-VFC Manual do produto - Página 8
Procurar online ou descarregar pdf Manual do produto para Acessórios CP Electronics ALC-PRM-VFC. CP Electronics ALC-PRM-VFC 8 páginas. Ceiling mounted photocell
Technical data
Dimensions
Weight
Supply Voltage
Frequency
Maximum Load
Power consumption
Terminal Capacity
Temperature
Humidity
Material (casing)
Type
IP rating
Compliance
Part numbers
Part number
Detector
ALC-PRM-VFC
Accessories
DBB
UHS5
UNLCDHS
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE Wiring
Regulations and any applicable Building Regulations.
8
See diagrams opposite
0.1kg
230VAC +/- 10%
50Hz
10 Amp resistive and incandescent lighting
6 Amp fluorescent lighting and resistive
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary
of transformer)
Fluorescent lighting (max 6 fittings
recommended)
For fluorescent lighting total power factor
correction capacitance must not exceed
40μF.
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
Minimum load 100mA
On 745mW, Off 264mW
2
2.5mm
-10ºC to 35ºC
5 to 95% non-condensing
Flame retardant ABS and PC/ABS
Class 2
IP40
EMC-2004/108/EC
LVD-2006/95/EC
Description
Ceiling Mounted Photocell
Surface mounting box
Programming IR handset
Universal LCD IR handset
ALC-PRM-VFC
DBB