Ensure that the builders opening, Flue & hearth for the appliance are constructed from non-combustible
materials and conform to National Regulations and Local Codes
All Models require a minimum flue diameter of 175mm or equivalent area (Class I)
The flue MUST be free of any obstructions. Any dampers or restrictors MUST be removed or dampers
must be fixed in some way in the OPEN position.
The chimney/flue should be swept prior to installation of the appliance.
Ensure that only one fireplace is served.
Ensure that the chimney/flue is continuous from inlet to terminal
Ensure that the chimney/flue is structurally sound, so that combustion products do not come into
contact with combustible material outside the chimney.
Ensure that there is a smooth tapered transition from the fireplace opening to the flue.
If the appliance is to be installed under a canopy, or is open on both sides, great care must be taken to
ensure the configuration is correct. If in any doubt seek expert advice.
CHECK FLUE PULL. Apply a smoke match to the flue opening at hearth level and observe smoke. If
there is a definite flow into the flue aperture, proceed with installation. If there is not a definite flow
into the flue aperture, preheat the flue for approximately 10 minutes and re-test. If there is still no
definite flow towards the flue aperture the flue may need attention and expert advice must be sort.
THE CONNECTION, VENTILLATION REQUIREMENTS (IF ANY) AND INSTALLATION OF THE
APPLIANCE MUST BE IN ACCORDANCE WITH NATIONAL REGULATIONS AND LOCAL CODES. IF IN
ANY DOUBT WITH REGARD TO ANY VENTILATION REQUIREMENTS SEED EXPERT ADVICE.
NOTE:
UK Model Numbers 1N, & 1L, do not require additional room ventilation.
In EIRE all Evolution fires require additional room ventilation.
For all other countries refer to National Regulations and Local Codes.