Dell EMC PowerEdge R640 Manual - Página 41

Procurar online ou descarregar pdf Manual para Servidor Dell EMC PowerEdge R640. Dell EMC PowerEdge R640 49 páginas. Metro node
Também para Dell EMC PowerEdge R640: Manual de instalação do hardware (2 páginas)

Dell EMC PowerEdge R640 Manual
Topics:

Power supply specifications

Chassis dimensions
Environmental specifications
Video specifications
Power supply specifications
The PowerEdge R640 systems support up to two AC or DC power supply units (PSUs).
Table 21. PSU specifications
PSU
Class
495 W AC
Platinum
750 W AC
Platinum
750 W AC
Titanium
750 W Mixed
Platinum
Mode HVDC—
for China only
1100 W AC
Platinum
1100 W Mixed
Platinum
Mode HVDC—
for China and
Japan only
1600 W AC
Platinum
Table 22. PSU specifications
PSU
Class
750 W Mixed Mode HVDC
NA
—for China only
1100 W DC
NA

Appendix A. Additional specifications

Heat dissipation—
Frequency
maximum
1908 BTU/hr
50/60 Hz
2891 BTU/hr
2843 BTU/hr
2891 BTU/hr
4100 BTU/hr
4100 BTU/hr
6000 BTU/hr
Heat dissipation—
maximum
2891 BTU/hr
4416 BTU/hr
Voltage
Current
100–240 V AC, autoranging 6.5 A – 3 A
100–240 V AC, autoranging 10 A – 5 A
200–240 V AC,
5 A
autoranging
100–240 V AC, autoranging 10 A – 5 A
100–240 V AC, autoranging 12 A – 6.5 A
100–240 V AC, autoranging 12 A – 6.5 A
100–240 V AC, autoranging 10 A
Frequency
Voltage
50/60 Hz
240 V DC,
autoranging
–(48–60) V DC,
autoranging
Appendix A. Additional specifications
11
Current
4.5 A
32 A
41