Dell PowerEdge C6100 Utilizar a instrução - Página 42

Procurar online ou descarregar pdf Utilizar a instrução para Servidor Dell PowerEdge C6100. Dell PowerEdge C6100 48 páginas. Poweredge series
Também para Dell PowerEdge C6100: Manual da carteira (27 páginas)

Dell PowerEdge C6100 Utilizar a instrução

Power Throttling Configuration in BIOS Setup Utility

Before enabling the power throttling feature, you must set the Power Management option to
Active Power Controller or Node Management. Access this option through the BIOS setup
utility's Server menu. Then from the Server menu you can enable or disable power throttling and
power CAP, and set the chassis CAP value.
Only MB4 can display the power throttling behavior setting in the BIOS setup menu.

Additional Power Throttling Information

The power throttling feature takes advantage of the node management function to control
CPU frequency.
If the chassis CAP function is disabled and power throttling is enabled, the BMC will set a
power supply unit (PSU) limit of one as the chassis CAP value.
After the power throttling and chassis CAP settings are changed, the main logic board (MLB)
must be restarted.
The power cap feature cannot be enabled concurrently with the Intel
(DCM).

Power Throttling Protection

The power throttling feature is a full power redundancy feature. This feature adjusts CPU
frequency via a PROCHOT# signal to reduce the MLB's power consumption.

Information From the Fan Control Board

BMC can get the following information from the fan control board:
FW version
Board ID
Ambient1 Reading
Ambient2 Reading
Fan Tach1 Reading
Fan Tach2 Reading
Fan Tach3 Reading
Fan Tach4 Reading
PSU Current Reading
42
Using the Baseboard Management Controller
®
Data Center Manager