Dell PowerEdge R420xr Manual de iniciação - Página 9
Procurar online ou descarregar pdf Manual de iniciação para Servidor Dell PowerEdge R420xr. Dell PowerEdge R420xr 10 páginas.
Environmental
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental conditions will be the
responsibility of the customer.
Air Filtration
NOTE: Applies to data center environments
only. Air filtration requirements do not apply
to IT equipment designed to be used outside
a data center, in environments such as an
office or factory floor.
Conductive Dust
NOTE: Applies to data center and non-data
center environments.
Corrosive Dust
NOTE: Applies to data center and non-data
center environments.
Gaseous Contamination
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper Coupon Corrosion Rate
Silver Coupon Corrosion Rate
Data center air filtration as defined by ISO Class
8 per ISO 14644-1 with a 95% upper confidence
limit.
NOTE: Air entering the data center must
have MERV11 or MERV13 filtration.
Air must be free of conductive dust, zinc
whiskers, or other conductive particles.
•
Air must be free of corrosive dust.
•
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
9