1U tool-less configuration
NOTE:
Your system is not NEBS Earthquake Z4-compliant if you use the 1U tool-less
square-hole or two-post installation methods.
1
Face the ReadyRails flange ears outward then place the rail between the left and right
vertical posts.
Align and seat the back flange rail pegs in the back vertical post flange. To see how the
pegs appear in both the square and unthreaded round holes, see item 1.
2
Align and seat the front flange pegs in the holes on the front side of the vertical post.
3
Repeat this procedure for the second rail.
4
Pull on the latch release button on each flange ear to remove each rail then unseat each
rail.
Figure 4. 1U tool-less configuration
12
Hardware installation