Allmatic CT INVERTER AM Manual de instalação - Página 9
Procurar online ou descarregar pdf Manual de instalação para Unidade de controlo Allmatic CT INVERTER AM. Allmatic CT INVERTER AM 12 páginas. Programmable control board for sliding gates with inverter technology
6.2 Learning the partial run (Menu B – Ped. Position)
Learning the partial run allows to define the position of partial opening that allows the pedestrians accessing (PED command)
Check that the adjustment of the torque and the speed of the gate are set before carrying out the learning phase.
Check that the gate is closed before starting the learning phase.
Enter the parameter Ped. Position of MENU
B and confirm by pressing key P2
Exit the menu by scrolling the entries until you
find EXIT
7 Adjustment of the speed and the torque (Menu B - Speed and torque)
The entries of menu B - Speed and torque - once the parameters themselves are entered allow to adjust the corresponding parameters from a
minimum up to a maximum value, according to the indications shown on the display.
The versatility of the control board allows an infinity of possible combinations: however it is recommended to adjust the settings by keeping into
account the dimensions and weight of the gate. High speeds may be dangerous, as well as high torques.
Such regulations must be carried out only by professionals.
It is recommended to check the correct functioning of the automation after any regulation.
It is highly recommended to learn the runs of the gate each time these parameters are changed.
8. Advanced functions
These are functions and/or functional modalities that can be activated by the user through the programming menu.
Automatic closing
Timed closing of the gate from totally open position or partial opening position. The "stop" command disables the automatic closing until a new
command given by the user is received (S.S., CLOSE, etc).
PhotoAutoReclose
The gate closes 3 seconds after the photocell intervenes in case the gate is in a totally open or in a partial open position.
Motor brake
To be used with motors with a strong inertia and the necessity to quickly stop the automation. Pay attention as the mechanics must be sized
accordingly.
OFF: Brake disabled
1: Electronic braking function
2: Activation of the contact on the auxiliary card for an external brake, active with still motor
3: Activation of the contact on the auxiliary card for an external brake, active when motor is moving
Dead Man
The motor moves only with permanent a command and not with just impulses: the motor opens if the key "open" is kept pressed, and the opposite
operation applies with the key "close". WARNING: this modality forbids all operations of automatic motion!
Condominium
All commands given via radio or by a step-by-step and/or a partial opening keys involve only the opening of the gate. The closing is related to the
function of automatic closing, which MUST BE ABSOLUTELY ACTIVATED since every command of closing is ignored.
Inv. On photocells
Allows to set if, once the photocell beam is interrupted, the gate must reverse immediately (only in closing) or just after the removal of the obstacle
(it applies both in opening and in closing)
Photocell test
This control unit is equipped with a function which allows to control the proper functioning of photocells before any operation of the motor is made.
The security of the system is therefore higher in case the photo-device breaks down (for example, if the relay of exit is stuck) or there is a
undesired short circuit on the input of the photocells. The control board indicates a possible fault by flashing only once when any key is pressed
and also by not moving at all. This check is made after the control board receives a command to move, but before the control board itself gives
power to the motor.
Edge Inv.
Allows to set if, once the safety edge alarms itself, the gate must stop or it must stop and then reverse (applies only in the phase of closing)
Edge Test
Functional test of the safety edge. Connect the safety edge as shown in the instructions by using the photocell test's clamp.
6-1622595
rev.06
13/01/2017
Start moving the gate by pressing and releasing key P1 (START) or a
Step-by-Step key.
When the gate reaches the position of partial opening, then push key
P1 (START) or a step-by-step key
The gate moves again in closing.
When the gate hits the limit in closing, then the programming is
terminated.
ITA
ENG
FRA
ESP
DEU
POR
9 / 12