Dialight Reliant Instruções de funcionamento e instalação - Página 4
Procurar online ou descarregar pdf Instruções de funcionamento e instalação para Equipamento de DJ Dialight Reliant. Dialight Reliant 14 páginas. High bay
480 VAC THREE PHASE – NORTH AMERICA
SYMBOL
COLOR
GREEN
L2
RED
L1
BLACK
DIM +
VIOLET
DIM -
GREY
100-277 VAC BATTERY BACKUP SWITCH LIVE
– NORTH AMERICA
SYMBOL
COLOR
GREEN
L
BLACK
PERMANENT LIVE
L'
YELLOW
N
WHITE
DIM +
VIOLET
DIM -
GREY
NOTE: For maintained battery backup, connect
the black wire to the supply permanent live and
the yellow wire to the supply switch live. For
sustained battery backup, connect both the
yellow and black wires to the supply live.
WARNING:
To be installed and/or used in accordance with
appropriate electrical codes and regulations.
To avoid fire and electrical shock, turn off power
at circuit breaker or fuse and test that the power
is off before wiring.
0-10VDC Dimming (If Applicable)
Dimming is controlled by means of a 0-10 VDC
signal (to be provided by the installer) to control
the level of dimming. At 10 volts, the output of
the unit is 100%; at 0 volts, the output will shut off.
The DC dimming voltage should not exceed 15
VDC. Increasing the voltage from 10VDC to
15VDC will not result in additional light output.
WARNING: Never connect the dimming wires to
the Hot or Neutral supply wires.
Variable Voltage Control
An analog 0-10 V active dimmer may be
connected to the two wires to control the light
output of the fixture.
Multiple lights may be
connected to the same dimmer, as long as the
maximum current rating of the dimmer is not
exceeded.
The dimmer must be capable of sinking 0.5 mA
per light. Light output will vary approximately
linearly
with
control
voltage,
corresponding to 100% light output.
NOTE: Simply shorting the two wires together will
cause the light to shut off.
Page
4
Reliant High Bay Americas – UL1598
Taking into Operation
Prior to operating, check the luminaire for its
CONNECTION
correct installation in compliance with these
EARTH
operating instructions and other applicable
LINE 2
regulations.
LINE 1
Conditions for Use
DIMMING
The supply to the luminaire must include a fuse
DIMMING
or circuit breaker that is capable of interrupting
a 1.5 kA short circuit current.
For maximum long-term reliability and light
output, the luminaire must be installed in free air.
CONNECTION
EARTH
WARNING: Improper installation, operation, or
maintenance of this luminaire may result in the
SWITCH LIVE
invalidation of the warranty, certificate, or
NEUTRAL
declaration of conformity.
DIMMING
Maintenance
DIMMING
This LED luminaire should require a minimum
amount of maintenance. If any unforeseen
repairs are required, please contact Dialight or
its authorized representative.
Inspection
Within the scope of maintenance or inspection
routine, the following should be included:
Protective hoses should be covering the
connection cables.
Cable entries must be free of corrosion.
The lens should be cleaned periodically as
needed to ensure continued photometric
performance. Clean the lens with a damp,
non-abrasive, lint free cloth. If not sufficient,
use mild soap.
Inspect the luminaire to ensure that it is free of
any
obstructions or contamination (i.e.
excessive dust build up). Clean with a non-
abrasive cloth if needed.
Perform visual mechanical and electrical
inspections
recommend routine checks to be made on a
yearly
environment should determine this.
It is recommended to follow an Electrical
Preventive
described in NFPA 70B: Recommended
Practice for Electrical Equipment.
Repairs / Overhaul / Modification
The equipment must be operated according to
the intended purpose in an undamaged
condition.
NOTE: Should the luminaire enclosure be
damaged, only a full luminaire replacement will
be permitted. In case of doubt, the equipment
with
10
V
should
inspection/repair.
Upgradable/Replacement Parts
The following are offered from Dialight as field
upgradable or replaceable parts:
Lenses, Drivers, Surge Protectors, Battery Backup
Systems, Battery Packs, Occupancy Sensors,
Wireless Controls Modules.
Contact Dialight for all necessary installation
instructions
upgradable parts.
on
a
regular
basis.
basis.
Frequency
of
use
Maintenance
Program
be
returned
to
Dialight
pertaining
to
replacement
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
Tel: 732 919 3119
Uplight
When equipped with factory-installed uplight,
luminaires will provide approximately 10% of
downlight lumens upwards.
Occupancy Sensors
Optionally occupancy sensors will dim or turn off
the luminaire when an area is not occupied.
They are available in manual control or
Bluetooth enabled models. See manufacturer
website for additional information (Legrand
Wattstopper)
For
model
RHU*****(E)*****
instructions at the link below:
www.legrand.us/wattstopper/fixtures-sensors-
and-controls/fixture-sensors/fsp3x1b.aspx
For
model
RHU*****(G)*****
instructions at the link below:
www.legrand.us/wattstopper/fixtures-sensors-
and-controls/fixture-sensors/fsp-3x1.aspx
For
model
RHU*****(F)*****
instructions at the link below:
www.legrand.us/wattstopper/fixtures-sensors-
and-controls/fixture-sensors/fsp-2x2.aspx
Battery Backup
If luminaire is equipped with battery backup,
connect the 4-position battery plug to the
battery driver. Battery backup modules come
with an indicator light/test switch. To test battery
function, press and hold test button to enter
battery backup mode. For indicator light
functions see table below.
LED Indicator Status
Solid Green
Slow Flashing Red
4s on / 1s off
Flashing Red
We
1s on / 1s off
Flashing Green
and
2s on / 2s off
Fast Flashing Red
0.1s on / 0.1s off
None. Both LED's off
as
Very Slow Flashing
Red
1s on / 7s off
*OTM=Over Temp Protection; ensures max
temperature ratings are not exceeded.
Wireless Controls
For luminaires equipped with wireless controls
capabilities, refer to the Dialight IntelliLED
Gateway Quick Start Guide for operating
instructions.
for
Surge Protection
Luminaires with additional surge protection will
have 10kV surge capabilities. If a surge is
encountered, the module will prevent the
luminaire from turning on and will need to be
replaced.
Disposal & Recycling
When the apparatus is disposed of, the
respective
national
disposal should be observed.
or
Fax: 732 751 5778
see
operating
see
operating
see
operating
EM Driver Status/Mode
System OK/AC OK
Battery not detected,
check connections
Battery Failure
Replace Battery
Self-Diagnostic
Test Underway
Abnormal Driver Perf
Replace Driver
Normal working in
EM Mode
OTM or other internal
protections triggered
TM
regulations
on
waste
9100RHB005000 REV C
www.dialight.com