Miller Bobcat 250 Manual de aplicação - Página 14

Procurar online ou descarregar pdf Manual de aplicação para Inversor Miller Bobcat 250. Miller Bobcat 250 16 páginas. Generator power

Miller Bobcat 250 Manual de aplicação

12. Selecting Extension Cord (Use Shortest Cord Possible)

Y If unit does not have GFCI receptacles, use GFCI-protected extension cord.
Current In
Load In
Amperes
Watts
5
7
10
1200
15
1800
20
2400
25
3000
30
3600
35
4200
40
4800
45
5400
50
6000
*Conductor size is based on maximum 2% voltage drop
Page 10
Cord Lengths For 120 Volt Loads
Maximum Allowable Cord Length In Feet (Meters)
4
600
840
400
(122)
300 (91)
225 (68)
175 (53)
150 (46)
125 (38)
112 (34)
100 (30)
87 (26)
For Conductor Size (AWG)*
6
8
350
(106)
400
250 (76)
(122)
275 (84)
175 (53)
175 (53)
112 (34)
137 (42)
87 (26)
112 (34)
62 (19)
87 (26)
50 (15)
75 (23)
50 (15)
62 (19)
37 (11)
62 (19)
50 (15)
10
12
225 (68)
137 (42)
150 (46)
100 (30)
112 (34)
62 (19)
75 (23)
37 (11)
50 (15)
30 (9)
37 (11)
37 (11)
14
100 (30)
62 (19)
50 (15)
30 (9)